DEMO - Signal Ridge Workshop
Fictional 12,000 sf fabrication workshop with 480 V machinery, overhead lighting and a 208/120 V support area. Demonstration data only; no real client, person or address is represented.
FBC, Energy Conservation, 8th Edition (2023), C405.5.3: feeders and branch circuits combined sized for at most 5 percent voltage drop.
- Pass
- 21
- Fail
- 0
- REQ
- 0
- Not calculated
- 0
26 Table 9 values used here are not yet checked against the book. They still compute; rows that use one are marked.
- NFPA-70-2020/Chapter 9/Table 9/AC Resistance Uncoated Copper Steel Conduit/4/0 AWG Unreviewed data: NEC 2020 Chapter 9, Table 9, AC Resistance Uncoated Copper Steel Conduit, 4/0 AWG (0.063 ohms per 1000 ft) has not been checked against the book.
- NFPA-70-2020/Chapter 9/Table 9/XL Steel Conduit/4/0 AWG Unreviewed data: NEC 2020 Chapter 9, Table 9, XL Steel Conduit, 4/0 AWG (0.051 ohms per 1000 ft) has not been checked against the book.
- NFPA-70-2020/Chapter 9/Table 9/AC Resistance Uncoated Copper Steel Conduit/8 AWG Unreviewed data: NEC 2020 Chapter 9, Table 9, AC Resistance Uncoated Copper Steel Conduit, 8 AWG (0.78 ohms per 1000 ft) has not been checked against the book.
- NFPA-70-2020/Chapter 9/Table 9/XL Steel Conduit/8 AWG Unreviewed data: NEC 2020 Chapter 9, Table 9, XL Steel Conduit, 8 AWG (0.065 ohms per 1000 ft) has not been checked against the book.
- NFPA-70-2020/Chapter 9/Table 9/AC Resistance Uncoated Copper Steel Conduit/3 AWG Unreviewed data: NEC 2020 Chapter 9, Table 9, AC Resistance Uncoated Copper Steel Conduit, 3 AWG (0.25 ohms per 1000 ft) has not been checked against the book.
- NFPA-70-2020/Chapter 9/Table 9/XL Steel Conduit/3 AWG Unreviewed data: NEC 2020 Chapter 9, Table 9, XL Steel Conduit, 3 AWG (0.059 ohms per 1000 ft) has not been checked against the book.
- NFPA-70-2020/Chapter 9/Table 9/AC Resistance Uncoated Copper Steel Conduit/6 AWG Unreviewed data: NEC 2020 Chapter 9, Table 9, AC Resistance Uncoated Copper Steel Conduit, 6 AWG (0.49 ohms per 1000 ft) has not been checked against the book.
- NFPA-70-2020/Chapter 9/Table 9/XL Steel Conduit/6 AWG Unreviewed data: NEC 2020 Chapter 9, Table 9, XL Steel Conduit, 6 AWG (0.064 ohms per 1000 ft) has not been checked against the book.
- NFPA-70-2020/Chapter 9/Table 9/AC Resistance Uncoated Copper Steel Conduit/12 AWG Unreviewed data: NEC 2020 Chapter 9, Table 9, AC Resistance Uncoated Copper Steel Conduit, 12 AWG (2.0 ohms per 1000 ft) has not been checked against the book.
- NFPA-70-2020/Chapter 9/Table 9/XL Steel Conduit/12 AWG Unreviewed data: NEC 2020 Chapter 9, Table 9, XL Steel Conduit, 12 AWG (0.068 ohms per 1000 ft) has not been checked against the book.
- NFPA-70-2020/Chapter 9/Table 9/AC Resistance Uncoated Copper Steel Conduit/10 AWG Unreviewed data: NEC 2020 Chapter 9, Table 9, AC Resistance Uncoated Copper Steel Conduit, 10 AWG (1.2 ohms per 1000 ft) has not been checked against the book.
- NFPA-70-2020/Chapter 9/Table 9/XL Steel Conduit/10 AWG Unreviewed data: NEC 2020 Chapter 9, Table 9, XL Steel Conduit, 10 AWG (0.063 ohms per 1000 ft) has not been checked against the book.
- NFPA-70-2020/Chapter 9/Table 9/AC Resistance Uncoated Copper Steel Conduit/4 AWG Unreviewed data: NEC 2020 Chapter 9, Table 9, AC Resistance Uncoated Copper Steel Conduit, 4 AWG (0.31 ohms per 1000 ft) has not been checked against the book.
- NFPA-70-2020/Chapter 9/Table 9/XL Steel Conduit/4 AWG Unreviewed data: NEC 2020 Chapter 9, Table 9, XL Steel Conduit, 4 AWG (0.060 ohms per 1000 ft) has not been checked against the book.
- NFPA-70-2020/Chapter 9/Table 9/AC Resistance Uncoated Copper Steel Conduit/2 AWG Unreviewed data: NEC 2020 Chapter 9, Table 9, AC Resistance Uncoated Copper Steel Conduit, 2 AWG (0.20 ohms per 1000 ft) has not been checked against the book.
- NFPA-70-2020/Chapter 9/Table 9/XL Steel Conduit/2 AWG Unreviewed data: NEC 2020 Chapter 9, Table 9, XL Steel Conduit, 2 AWG (0.057 ohms per 1000 ft) has not been checked against the book.
- NFPA-70-2020/Chapter 9/Table 9/AC Resistance Uncoated Copper Steel Conduit/1 AWG Unreviewed data: NEC 2020 Chapter 9, Table 9, AC Resistance Uncoated Copper Steel Conduit, 1 AWG (0.16 ohms per 1000 ft) has not been checked against the book.
- NFPA-70-2020/Chapter 9/Table 9/XL Steel Conduit/1 AWG Unreviewed data: NEC 2020 Chapter 9, Table 9, XL Steel Conduit, 1 AWG (0.057 ohms per 1000 ft) has not been checked against the book.
- NFPA-70-2020/Chapter 9/Table 9/AC Resistance Uncoated Copper Steel Conduit/1/0 AWG Unreviewed data: NEC 2020 Chapter 9, Table 9, AC Resistance Uncoated Copper Steel Conduit, 1/0 AWG (0.12 ohms per 1000 ft) has not been checked against the book.
- NFPA-70-2020/Chapter 9/Table 9/XL Steel Conduit/1/0 AWG Unreviewed data: NEC 2020 Chapter 9, Table 9, XL Steel Conduit, 1/0 AWG (0.055 ohms per 1000 ft) has not been checked against the book.
- NFPA-70-2020/Chapter 9/Table 9/AC Resistance Uncoated Copper Steel Conduit/2/0 AWG Unreviewed data: NEC 2020 Chapter 9, Table 9, AC Resistance Uncoated Copper Steel Conduit, 2/0 AWG (0.10 ohms per 1000 ft) has not been checked against the book.
- NFPA-70-2020/Chapter 9/Table 9/XL Steel Conduit/2/0 AWG Unreviewed data: NEC 2020 Chapter 9, Table 9, XL Steel Conduit, 2/0 AWG (0.054 ohms per 1000 ft) has not been checked against the book.
- NFPA-70-2020/Chapter 9/Table 9/AC Resistance Uncoated Copper Steel Conduit/3/0 AWG Unreviewed data: NEC 2020 Chapter 9, Table 9, AC Resistance Uncoated Copper Steel Conduit, 3/0 AWG (0.079 ohms per 1000 ft) has not been checked against the book.
- NFPA-70-2020/Chapter 9/Table 9/XL Steel Conduit/3/0 AWG Unreviewed data: NEC 2020 Chapter 9, Table 9, XL Steel Conduit, 3/0 AWG (0.052 ohms per 1000 ft) has not been checked against the book.
- NFPA-70-2020/Chapter 9/Table 9/AC Resistance Uncoated Copper Steel Conduit/14 AWG Unreviewed data: NEC 2020 Chapter 9, Table 9, AC Resistance Uncoated Copper Steel Conduit, 14 AWG (3.1 ohms per 1000 ft) has not been checked against the book.
- NFPA-70-2020/Chapter 9/Table 9/XL Steel Conduit/14 AWG Unreviewed data: NEC 2020 Chapter 9, Table 9, XL Steel Conduit, 14 AWG (0.073 ohms per 1000 ft) has not been checked against the book.
Scroll each table sideways for the drop, allowance and state columns.
| Equipment | Fed from | Length (ft) | Size | Drop | Allowance | Cumulative |
|---|---|---|---|---|---|---|
| DP-W1Panel | U-5 | 40 | 4/0 AWG | 0.26 %Uses 2 unreviewed Table 9 values1.26 V | 2.00 % | Not countedabove the start point |
| T-1Transformer | DP-W1 | 25 | 8 AWG | 0.32 %Uses 2 unreviewed Table 9 values1.53 V | 2.00 % | 0.32 %Uses 2 unreviewed Table 9 valuesfrom DP-W1 |
| LP-W1Panel | T-1 | 10 | 3 AWG | 0.21 %Uses 2 unreviewed Table 9 values0.44 V | 2.00 % | 0.53 %Uses 4 unreviewed Table 9 valuesfrom DP-W1 |
DP-W1
| Ckt | Description | Length (ft) | Current | Size | Drop | Allowance | Min size | Combined | State |
|---|---|---|---|---|---|---|---|---|---|
| 1,3,5 | CNC machining center | 120 | 48.00 A80 % of trip | 6 AWG | 1.03 %Uses 2 unreviewed Table 9 values4.93 V | 3.00 % | 10 AWGUses 24 unreviewed Table 9 values | 1.03 %Uses 2 unreviewed Table 9 values | Pass |
| 2,4,6 | Dust collection system | 150 | 32.00 A80 % of trip | 8 AWG | 1.36 %Uses 2 unreviewed Table 9 values6.51 V | 3.00 % | 10 AWGUses 24 unreviewed Table 9 values | 1.36 %Uses 2 unreviewed Table 9 values | Pass |
| 7,9,11 | Shop air compressor | 90 | 32.00 A80 % of trip | 8 AWG | 0.81 %Uses 2 unreviewed Table 9 values3.90 V | 3.00 % | 12 AWGUses 26 unreviewed Table 9 values | 0.81 %Uses 2 unreviewed Table 9 values | Pass |
| 8,10,12 | Workshop HVAC unit | 60 | 40.00 A80 % of trip | 8 AWG | 0.68 %Uses 2 unreviewed Table 9 values3.25 V | 3.00 % | 14 AWGUses 26 unreviewed Table 9 values | 0.68 %Uses 2 unreviewed Table 9 values | Pass |
| 14,16,18 | Assembly station equipment | 110 | 24.00 A80 % of trip | 10 AWG | 1.14 %Uses 2 unreviewed Table 9 values5.49 V | 3.00 % | 14 AWGUses 26 unreviewed Table 9 values | 1.14 %Uses 2 unreviewed Table 9 values | Pass |
| 19 | 277 V high-bay lighting - A | 140 | 16.00 A80 % of trip | 10 AWG | 1.94 %Uses 2 unreviewed Table 9 values5.38 V | 3.00 % | 10 AWGUses 24 unreviewed Table 9 values | 1.94 %Uses 2 unreviewed Table 9 values | Pass |
| 21 | 277 V high-bay lighting - B | 160 | 16.00 A80 % of trip | 10 AWG | 2.22 %Uses 2 unreviewed Table 9 values6.15 V | 3.00 % | 10 AWGUses 24 unreviewed Table 9 values | 2.22 %Uses 2 unreviewed Table 9 values | Pass |
| 23 | 277 V high-bay lighting - C | 180 | 16.00 A80 % of trip | 10 AWG | 2.50 %Uses 2 unreviewed Table 9 values6.92 V | 3.00 % | 10 AWGUses 24 unreviewed Table 9 values | 2.50 %Uses 2 unreviewed Table 9 values | Pass |
| 20 | 277 V exterior lighting | 120 | 16.00 A80 % of trip | 12 AWG | 2.77 %Uses 2 unreviewed Table 9 values7.68 V | 3.00 % | 12 AWGUses 26 unreviewed Table 9 values | 2.77 %Uses 2 unreviewed Table 9 values | Pass |
LP-W1
| Ckt | Description | Length (ft) | Current | Size | Drop | Allowance | Min size | Combined | State |
|---|---|---|---|---|---|---|---|---|---|
| 1 | Tool receptacles - bench A | 60 | 16.00 A80 % of trip | 10 AWG | 1.92 %Uses 2 unreviewed Table 9 values2.31 V | 3.00 % | 10 AWGUses 24 unreviewed Table 9 values | 2.45 %Uses 6 unreviewed Table 9 values | Pass |
| 2 | Tool receptacles - bench B | 75 | 16.00 A80 % of trip | 10 AWG | 2.40 %Uses 2 unreviewed Table 9 values2.88 V | 3.00 % | 10 AWGUses 24 unreviewed Table 9 values | 2.93 %Uses 6 unreviewed Table 9 values | Pass |
| 3 | Office receptacles | 40 | 16.00 A80 % of trip | 12 AWG | 2.13 %Uses 2 unreviewed Table 9 values2.56 V | 3.00 % | 12 AWGUses 26 unreviewed Table 9 values | 2.67 %Uses 6 unreviewed Table 9 values | Pass |
| 4 | Breakroom counter | 45 | 16.00 A80 % of trip | 12 AWG | 2.40 %Uses 2 unreviewed Table 9 values2.88 V | 3.00 % | 12 AWGUses 26 unreviewed Table 9 values | 2.93 %Uses 6 unreviewed Table 9 values | Pass |
| 5 | Support area lighting | 50 | 16.00 A80 % of trip | 12 AWG | 2.67 %Uses 2 unreviewed Table 9 values3.20 V | 3.00 % | 12 AWGUses 26 unreviewed Table 9 values | 3.20 %Uses 6 unreviewed Table 9 values | Pass |
| 6 | Office lighting | 35 | 16.00 A80 % of trip | 12 AWG | 1.87 %Uses 2 unreviewed Table 9 values2.24 V | 3.00 % | 14 AWGUses 26 unreviewed Table 9 values | 2.40 %Uses 6 unreviewed Table 9 values | Pass |
| 7 | Dock door operator 1 | 90 | 16.00 A80 % of trip | 10 AWG | 2.88 %Uses 2 unreviewed Table 9 values3.46 V | 3.00 % | 10 AWGUses 24 unreviewed Table 9 values | 3.42 %Uses 6 unreviewed Table 9 values | Pass |
| 8 | Dock door operator 2 | 95 | 16.00 A80 % of trip | 8 AWG | 1.98 %Uses 2 unreviewed Table 9 values2.38 V | 3.00 % | 8 AWGUses 22 unreviewed Table 9 values | 2.51 %Uses 4 unreviewed Table 9 values | Pass |
| 9 | IT cabinet | 30 | 16.00 A80 % of trip | 12 AWG | 1.60 %Uses 2 unreviewed Table 9 values1.92 V | 3.00 % | 14 AWGUses 26 unreviewed Table 9 values | 2.13 %Uses 6 unreviewed Table 9 values | Pass |
| 10 | Restroom receptacles | 55 | 16.00 A80 % of trip | 12 AWG | 2.94 %Uses 2 unreviewed Table 9 values3.52 V | 3.00 % | 12 AWGUses 26 unreviewed Table 9 values | 3.47 %Uses 6 unreviewed Table 9 values | Pass |
| 11 | Breakroom refrigerator | 45 | 16.00 A80 % of trip | 12 AWG | 2.40 %Uses 2 unreviewed Table 9 values2.88 V | 3.00 % | 12 AWGUses 26 unreviewed Table 9 values | 2.93 %Uses 6 unreviewed Table 9 values | Pass |
| 12 | Janitor receptacle | 60 | 16.00 A80 % of trip | 10 AWG | 1.92 %Uses 2 unreviewed Table 9 values2.31 V | 3.00 % | 10 AWGUses 24 unreviewed Table 9 values | 2.45 %Uses 6 unreviewed Table 9 values | Pass |