LP-W1 (SUPPORT AREA ELECTRICAL CLOSET)
LP-W1
MAIN:M.C.B.RATING:100 ASPACES:30SERVICE: 120/208 V, 3-PHASE, 4-WIREMOUNTING: SURFACEFEEDS FROM: T-1 / 30 KVA / DP-W1 CIRCUITS 13,15,17PANEL SCCR: 10 KATRIM: HINGED DOOR, NEMA 1A.I.C.: 10 KAFAULT CURRENT CALCULATED 2026-11-22 / fnv1a32:83b01178AFC: 1.9 KA, uses Eaton Table 4 C values not yet checked against the bookA.I.C. PASS, SCCR PASS
Panel schedule for LP-W1, odd circuits on the left and even circuits on the right
CKTDESCRIPTIONKVACIRCUIT BREAKERBRANCH CIRCUITCVD%PHCKTDESCRIPTIONKVACIRCUIT BREAKERBRANCH CIRCUITCVD%PH
POLETRIPPNGNDPOLETRIPPNGND
11.8120101010--1.92A21.8120101010--2.40A
31.44120121212--2.13B41.5120121212--2.40B
50.72120121212--2.67C60.6120121212--1.87C
70.9120101010--2.88A80.9120888--1.98A
91.08120121212--1.60B101.2120121212--2.94B
110.72120121212--2.40C121.26120101010--1.92C
13----------------A14----------------A
15--120----------B16--120----------B
17----------------C18----------------C
19----------------A20----------------A
21----------------B22----------------B
23----------------C24----------------C
25----------------A26----------------A
27----------------B28----------------B
29----------------C30----------------C
CONNECTED LOAD: 13.92 KVAPHASE A: 45.0 APHASE B: 43.5 APHASE C: 27.5 AIMBALANCE: 45.3%
WORST COMBINED VOLTAGE DROP: 3.47% AT CKT 10, C405.5.3, uses Table 9 values not yet checked against the book
CALCULATED LOAD: 13.22 KVA (13.49 KVA CONTINUOUS AT 125%)MAXIMUM LOAD: 46.88 A, 47% OF 100 A MAIN, HEAVIEST LINE ACONTINUOUS AT 125%: 46.88 A, 47% OF 100 A MAIN, HEAVIEST LINE A
GENERAL LIGHTINGCOUNTED 1.32 KVADEMAND 1.65 KVATable 220.12 unit load or 125 % of connected, whichever is larger, then Table 220.42
RECEPTACLESCOUNTED 7.74 KVADEMAND 7.74 KVATable 220.44: first 10 kVA at 100 %, the rest at 50 %, with the 220.14(K) office minimum
MOTORCOUNTED 1.80 KVADEMAND 2.03 KVA220.50 and 430.24: every motor plus 25 % of the largest
OTHER (NAMEPLATE)COUNTED 1.80 KVADEMAND 1.80 KVA220.14(A): nameplate at 100 %
Unreviewed data: the calculated load uses NEC 2020 values not yet checked against the book: Table 220.12 (Office); Table 220.42 (All others, total factor); 220.14(I) (single or multiple receptacle on one yoke); Table 220.44 (first band limit, first band factor, remainder factor); 220.14(K) (office receptacle minimum).
NOTES: Synthetic demonstration schedule. Connected loads, run lengths, raceways, installed conductor sizes, load categories, served areas, equipment ratings, energy code scope and fault-current inputs are fictional. Table values are not yet checked against the book.
Unreviewed data: 3 C values from Eaton's Short-Circuit Current Calculations (2014), Table 4, three single conductors at 600 V, used on the runs to DP-W1, T-1 and LP-W1, not yet checked against the bulletin: copper in steel conduit: 4/0 AWG, 8 AWG, 3 AWG. get_fault_current lists each value and where it is used.

Calculated load

Calculated

13.22 kVA13.49 kVA with continuous loads at 125 %

Maximum load
46.88 A 47 % of the 100 A mainheaviest line A
Continuous at 125 %
46.88 A 47 % of the 100 A mainheaviest line A

At 208 V, three-phase.

Calculated load by category
CategoryCountedDemandRule
General lighting1.32 kVA1.65 kVATable 220.12 unit load or 125 % of connected, whichever is larger, then Table 220.42
Receptacles7.74 kVA7.74 kVATable 220.44: first 10 kVA at 100 %, the rest at 50 %, with the 220.14(K) office minimum
Motor1.80 kVA2.03 kVA220.50 and 430.24: every motor plus 25 % of the largest
Other (nameplate)1.80 kVA1.80 kVA220.14(A): nameplate at 100 %
  • Unreviewed data: 7 table values (Table 220.12, Table 220.42, 220.14(I), Table 220.44, 220.14(K)) not yet checked against the code book.