DP-W1 (MAIN ELECTRICAL ROOM)
DP-W1
MAIN:M.C.B.RATING:225 ASPACES:42SERVICE: 277/480 V, 3-PHASE, 4-WIREMOUNTING: SURFACEFEEDS FROM: UTILITY SERVICEPANEL SCCR: 14 KATRIM: HINGED DOOR, NEMA 1A.I.C.: 14 KAFAULT CURRENT CALCULATED 2026-11-22 / fnv1a32:83b01178AFC: 10.9 KA, uses Eaton Table 4 C values not yet checked against the bookA.I.C. PASS, SCCR PASS
Panel schedule for DP-W1, odd circuits on the left and even circuits on the right
CKTDESCRIPTIONKVACIRCUIT BREAKERBRANCH CIRCUITCVD%PHCKTDESCRIPTIONKVACIRCUIT BREAKERBRANCH CIRCUITCVD%PH
POLETRIPPNGNDPOLETRIPPNGND
130.03606--10--1.03A218.03408--10--1.36A
36----B48----B
56----C68----C
715.03408--10--0.81A824.03508--10--0.68A
98----B108----B
118----C128----C
1313.923458--10--0.32A1412.033010--10--1.14A
158----B1610----B
178----C1810----C
192.2120101010--1.94A201.1120121212--2.77A
212.2120101010--2.22B22----------------B
232.2120101010--2.50C24----------------C
25--120----------A26--120----------A
27----------------B28----------------B
29----------------C30----------------C
31----------------A32----------------A
33----------------B34----------------B
35----------------C36----------------C
37----------------A38----------------A
39----------------B40----------------B
41----------------C42----------------C
CONNECTED LOAD: 120.62 KVAPHASE A: 147.8 APHASE B: 143.8 APHASE C: 143.8 AIMBALANCE: 2.7%
WORST COMBINED VOLTAGE DROP: 2.77% AT CKT 20, C405.5.3, uses Table 9 values not yet checked against the book
CALCULATED LOAD: 138.90 KVA (142.44 KVA CONTINUOUS AT 125%)MAXIMUM LOAD: 174.41 A, 78% OF 225 A MAIN, HEAVIEST LINE ACONTINUOUS AT 125%: 179.01 A, 80% OF 225 A MAIN, HEAVIEST LINE A
GENERAL LIGHTINGCOUNTED 7.92 KVADEMAND 20.01 KVATable 220.12 unit load or 125 % of connected, whichever is larger, then Table 220.42
RECEPTACLESCOUNTED 7.74 KVADEMAND 7.74 KVATable 220.44: first 10 kVA at 100 %, the rest at 50 %, with the 220.14(K) office minimum
MOTORCOUNTED 88.76 KVADEMAND 96.25 KVA220.50 and 430.24: every motor plus 25 % of the largest
OTHER (NAMEPLATE)COUNTED 14.90 KVADEMAND 14.90 KVA220.14(A): nameplate at 100 %
Warning: The feeder circuit of DP-W1 that supplies T-1 has its own load component; the roll-up counts T-1's load instead.
Unreviewed data: the calculated load uses NEC 2020 values not yet checked against the book: Table 220.12 (Office, Workshop); Table 220.42 (All others, total factor); 220.14(I) (single or multiple receptacle on one yoke); Table 220.44 (first band limit, first band factor, remainder factor); 220.14(K) (office receptacle minimum).
NOTES: Synthetic demonstration schedule. Connected loads, run lengths, raceways, installed conductor sizes, load categories, served areas, equipment ratings, energy code scope and fault-current inputs are fictional. Table values are not yet checked against the book.
Unreviewed data: 1 C value from Eaton's Short-Circuit Current Calculations (2014), Table 4, three single conductors at 600 V, used on the run to DP-W1, not yet checked against the bulletin: copper in steel conduit: 4/0 AWG. get_fault_current lists each value and where it is used.

Calculated load

Calculated

138.90 kVA142.44 kVA with continuous loads at 125 %

Maximum load
174.41 A 78 % of the 225 A mainheaviest line A
Continuous at 125 %
179.01 A 80 % of the 225 A mainheaviest line A

At 480 V, three-phase.

Calculated load by category
CategoryCountedDemandRule
General lighting7.92 kVA20.01 kVATable 220.12 unit load or 125 % of connected, whichever is larger, then Table 220.42
Receptacles7.74 kVA7.74 kVATable 220.44: first 10 kVA at 100 %, the rest at 50 %, with the 220.14(K) office minimum
Motor88.76 kVA96.25 kVA220.50 and 430.24: every motor plus 25 % of the largest
Other (nameplate)14.90 kVA14.90 kVA220.14(A): nameplate at 100 %
  • The feeder circuit of DP-W1 that supplies T-1 has its own load component; the roll-up counts T-1's load instead.
  • Unreviewed data: 8 table values (Table 220.12, Table 220.42, 220.14(I), Table 220.44, 220.14(K)) not yet checked against the code book.