DP-W1 Panel Warning: feeder circuit load not counted.
Unreviewed data
119,323 138,895 (uses unreviewed table data) 174.41 179.01 174.41 (line A) 480 V 3-ph Calculated The figures below use 8 NEC 220
values not yet checked against the
code book, listed at the end.
Category breakdown Category Connected VA Demand VA Continuous at 125 % Rule General lightingTable 220.12 unit load or 125 % of connected, whichever is larger, then Table 220.42 7,920 20,010 20,010 Table 220.12 unit load or 125 % of connected, whichever is larger, then Table 220.42 ReceptaclesTable 220.44: first 10 kVA at 100 %, the rest at 50 %, with the 220.14(K) office minimum 7,740 7,740 7,740 Table 220.44: first 10 kVA at 100 %, the rest at 50 %, with the 220.14(K) office minimum Motor220.50 and 430.24: every motor plus 25 % of the largest 88,763 96,245 96,245 220.50 and 430.24: every motor plus 25 % of the largest Other (nameplate)220.14(A): nameplate at 100 % 14,900 14,900 18,445 220.14(A): nameplate at 100 %
Noncoincident loads (220.60) No noncoincident groups below this node.
Currents At 480 V, 3-phase, 3 poles, from the supply that feeds it.
Maximum load 174.41 A Balanced 167.07 A; heaviest line 174.41 (line A). The heaviest line governs.
Continuous at 125 % 179.01 A Balanced 171.33 A; heaviest line 179.01 (line A). The heaviest line governs. Warnings (1) The feeder circuit of DP-W1 that supplies T-1 has its own load component; the roll-up counts T-1's load instead. [LOAD_FEEDER_COMPONENTS_IGNORED] Unreviewed NEC 220 values (8) Transcribed from secondary sources and not yet checked against NFPA 70
(2020). They compute.
Table 220.12, Office uses 1.3 VA/ft² Table 220.42, All others, total factor uses 1 (demand factor) Table 220.12, Workshop uses 1.7 VA/ft² 220.14(I), single or multiple receptacle on one yoke uses 180 VA per yoke Table 220.44, first band limit uses 10000 VA Table 220.44, first band factor uses 1 (demand factor) Table 220.44, remainder factor uses 0.5 (demand factor) 220.14(K), office receptacle minimum uses 1 VA/ft² Open DP-W1 in the panel editor
T-1 Transformer Unreviewed data
12,660 13,215 (uses unreviewed table data) 20.31 20.31 20.31 (primary) 480 V 3-ph Calculated The figures below use 7 NEC 220
values not yet checked against the
code book, listed at the end.
Category breakdown Category Connected VA Demand VA Continuous at 125 % Rule General lightingTable 220.12 unit load or 125 % of connected, whichever is larger, then Table 220.42 1,320 1,650 1,650 Table 220.12 unit load or 125 % of connected, whichever is larger, then Table 220.42 ReceptaclesTable 220.44: first 10 kVA at 100 %, the rest at 50 %, with the 220.14(K) office minimum 7,740 7,740 7,740 Table 220.44: first 10 kVA at 100 %, the rest at 50 %, with the 220.14(K) office minimum Motor220.50 and 430.24: every motor plus 25 % of the largest 1,800 2,025 2,025 220.50 and 430.24: every motor plus 25 % of the largest Other (nameplate)220.14(A): nameplate at 100 % 1,800 1,800 2,070 220.14(A): nameplate at 100 %
Noncoincident loads (220.60) No noncoincident groups below this node.
Currents At 480 V, 3-phase, 3 poles, from the supply that feeds it.
Maximum load 20.31 A Balanced 15.90 A; heaviest line 20.31 (primary). The heaviest line governs. Primary: 20.31 A on every line.
Continuous at 125 % 20.31 A Balanced 16.22 A; heaviest line 20.31 (primary). The heaviest line governs. Primary: 20.31 A on every line.
Unreviewed NEC 220 values (7) Transcribed from secondary sources and not yet checked against NFPA 70
(2020). They compute.
Table 220.12, Office uses 1.3 VA/ft² Table 220.42, All others, total factor uses 1 (demand factor) 220.14(I), single or multiple receptacle on one yoke uses 180 VA per yoke Table 220.44, first band limit uses 10000 VA Table 220.44, first band factor uses 1 (demand factor) Table 220.44, remainder factor uses 0.5 (demand factor) 220.14(K), office receptacle minimum uses 1 VA/ft² LP-W1 Panel Unreviewed data
12,660 13,215 (uses unreviewed table data) 46.88 46.88 46.88 (line A) 208 V 3-ph Calculated The figures below use 7 NEC 220
values not yet checked against the
code book, listed at the end.
Category breakdown Category Connected VA Demand VA Continuous at 125 % Rule General lightingTable 220.12 unit load or 125 % of connected, whichever is larger, then Table 220.42 1,320 1,650 1,650 Table 220.12 unit load or 125 % of connected, whichever is larger, then Table 220.42 ReceptaclesTable 220.44: first 10 kVA at 100 %, the rest at 50 %, with the 220.14(K) office minimum 7,740 7,740 7,740 Table 220.44: first 10 kVA at 100 %, the rest at 50 %, with the 220.14(K) office minimum Motor220.50 and 430.24: every motor plus 25 % of the largest 1,800 2,025 2,025 220.50 and 430.24: every motor plus 25 % of the largest Other (nameplate)220.14(A): nameplate at 100 % 1,800 1,800 2,070 220.14(A): nameplate at 100 %
Noncoincident loads (220.60) No noncoincident groups below this node.
Currents At 208 V, 3-phase, 3 poles, from the supply that feeds it.
Maximum load 46.88 A Balanced 36.68 A; heaviest line 46.88 (line A). The heaviest line governs.
Continuous at 125 % 46.88 A Balanced 37.43 A; heaviest line 46.88 (line A). The heaviest line governs.
Unreviewed NEC 220 values (7) Transcribed from secondary sources and not yet checked against NFPA 70
(2020). They compute.
Table 220.12, Office uses 1.3 VA/ft² Table 220.42, All others, total factor uses 1 (demand factor) 220.14(I), single or multiple receptacle on one yoke uses 180 VA per yoke Table 220.44, first band limit uses 10000 VA Table 220.44, first band factor uses 1 (demand factor) Table 220.44, remainder factor uses 0.5 (demand factor) 220.14(K), office receptacle minimum uses 1 VA/ft² Open LP-W1 in the panel editor