DEMO - Signal Ridge Workshop
DEMO-26005Light industrial workshop505 Signal Ridge Road, Example City - fictional siteSchematic designCommercial energy code
Fictional 12,000 sf fabrication workshop with 480 V machinery, overhead lighting and a 208/120 V support area. Demonstration data only; no real client, person or address is represented.
3 runs use a C value
from Eaton Table 4 that is not yet checked against the book. Values that
depend on it are calculated and marked unreviewed.
Equipment and system
Available
Motor contribution
AIC 110.9
SCCR 408.6
Utility source · 277/480Y V 3Ø
12.1 kA
419 A
Not checked
Not checked
Utility source
Utility transformer
500 kVA, 5.75 %Z
Basis
Fictional demo value: a 500 kVA pad-mount utility transformer, not from any utility.
Motor contribution
Motors listed on the panels it feeds
Full-load current
601.41 A
%Z applied
5.1750
Multiplier
19.3237
Result
At the line terminals
12,040 A three-phase
Motor contribution
419 A
Panel · 277/480Y V 3ØService · 110.24
10.9 kAUnreviewed C value
419 A
14 kAPassunder 110.9
14 kAPassunder 408.6
Run from its supply
Run
40 ft, 1 × 4/0 AWG
copper, steel raceway
C value
15,082Eaton-Bussmann-Short-Circuit-Current-Calculations-2014/p. 242/Table 4/copper/three single conductors/steel conduit/600 V/4/0 AWG
Checked against the book
No: unreviewed data
f, M
0.1112, 0.8999
Result
At the line terminals
10,877 A three-phase
Motor contribution
419 A
Issues
WarningThe supply from U-5 to DP-W1: Unreviewed data: the C value for copper 4/0 AWG, three single conductors in steel conduit (Table 4 steel conduit column, 600 V) uses 15082, transcribed from Eaton's Short-Circuit Current Calculations (2014), Table 4, and not yet checked against the bulletin.C_VALUE_UNREVIEWED
Transformer · 277/480Y V 3Ø
Pri7.0 kASec1.9 kAUnreviewed C value
Pri419 ASec60 A
Not checked
Not checked
Run from its supply
Run
25 ft, 1 × 8 AWG
copper, steel raceway
C value
1,557Eaton-Bussmann-Short-Circuit-Current-Calculations-2014/p. 242/Table 4/copper/three single conductors/steel conduit/600 V/8 AWG
Checked against the book
No: unreviewed data
f, M
0.6059, 0.6227
Transformer
Rating
30 kVA
Primary, secondary
480 V 3Ø, 120/208Y V 3Ø
Nameplate %Z
4.5 %Z: Fictional demo value: an invented nameplate for T-1.
Motor contribution
Motors listed on the panels it feeds
Primary current
6,512.22 A
%Z applied
4.0500
f, M
7.3091, 0.1203
Secondary full-load current
83.27 A
Result
Primary
6,931 A three-phase
Secondary
1,869 A three-phase
Motor contribution
419 A
Secondary motor contribution
60 A
Issues
WarningThe feeder circuit "T-1 primary - 30 kVA transformer" of DP-W1 to T-1: Unreviewed data: the C value for copper 8 AWG, three single conductors in steel conduit (Table 4 steel conduit column, 600 V) uses 1557, transcribed from Eaton's Short-Circuit Current Calculations (2014), Table 4, and not yet checked against the bulletin.C_VALUE_UNREVIEWED
WarningThe supply from U-5 to DP-W1: Unreviewed data: the C value for copper 4/0 AWG, three single conductors in steel conduit (Table 4 steel conduit column, 600 V) uses 15082, transcribed from Eaton's Short-Circuit Current Calculations (2014), Table 4, and not yet checked against the bulletin.C_VALUE_UNREVIEWED
Panel · 120/208Y V 3Ø
1.9 kAUnreviewed C value
60 A
10 kAPassunder 110.9
10 kAPassunder 408.6
Run from its supply
Run
10 ft, 1 × 3 AWG
copper, steel raceway
C value
4,774Eaton-Bussmann-Short-Circuit-Current-Calculations-2014/p. 242/Table 4/copper/three single conductors/steel conduit/600 V/3 AWG
Checked against the book
No: unreviewed data
f, M
0.0315, 0.9694
Result
At the line terminals
1,814 A three-phase
Motor contribution
60 A
Issues
WarningThe supply from T-1 to LP-W1: Unreviewed data: the C value for copper 3 AWG, three single conductors in steel conduit (Table 4 steel conduit column, 600 V) uses 4774, transcribed from Eaton's Short-Circuit Current Calculations (2014), Table 4, and not yet checked against the bulletin.C_VALUE_UNREVIEWED
WarningThe supply from U-5 to DP-W1: Unreviewed data: the C value for copper 4/0 AWG, three single conductors in steel conduit (Table 4 steel conduit column, 600 V) uses 15082, transcribed from Eaton's Short-Circuit Current Calculations (2014), Table 4, and not yet checked against the bulletin.C_VALUE_UNREVIEWED
WarningThe feeder circuit "T-1 primary - 30 kVA transformer" of DP-W1 to T-1: Unreviewed data: the C value for copper 8 AWG, three single conductors in steel conduit (Table 4 steel conduit column, 600 V) uses 1557, transcribed from Eaton's Short-Circuit Current Calculations (2014), Table 4, and not yet checked against the bulletin.C_VALUE_UNREVIEWED