Forewit
Shared public demo. Use fictional data. Anyone can change these projects.Join the waitlistContact

DEMO - Meadow Commons Cafe

DEMO-26004Cafe and commercial kitchen404 Meadow Walk, Example City - fictional siteConstruction administrationCommercial energy code

Fictional 2,400 sf neighborhood cafe with 48 seats, electric cooking, espresso service and walk-in refrigeration. Demonstration data only; no real client, person or address is represented.

Combined voltage drop, 5.00 % limit

FBC, Energy Conservation, 8th Edition (2023), C405.5.3: feeders and branch circuits combined sized for at most 5 percent voltage drop.

Pass
22
Fail
0
REQ
0
Not calculated
0
26 Table 9 values used here are not yet checked against the book. They still compute; rows that use one are marked.
  • NFPA-70-2020/Chapter 9/Table 9/AC Resistance Uncoated Copper Steel Conduit/4/0 AWG Unreviewed data: NEC 2020 Chapter 9, Table 9, AC Resistance Uncoated Copper Steel Conduit, 4/0 AWG (0.063 ohms per 1000 ft) has not been checked against the book.
  • NFPA-70-2020/Chapter 9/Table 9/XL Steel Conduit/4/0 AWG Unreviewed data: NEC 2020 Chapter 9, Table 9, XL Steel Conduit, 4/0 AWG (0.051 ohms per 1000 ft) has not been checked against the book.
  • NFPA-70-2020/Chapter 9/Table 9/AC Resistance Uncoated Copper Steel Conduit/3 AWG Unreviewed data: NEC 2020 Chapter 9, Table 9, AC Resistance Uncoated Copper Steel Conduit, 3 AWG (0.25 ohms per 1000 ft) has not been checked against the book.
  • NFPA-70-2020/Chapter 9/Table 9/XL Steel Conduit/3 AWG Unreviewed data: NEC 2020 Chapter 9, Table 9, XL Steel Conduit, 3 AWG (0.059 ohms per 1000 ft) has not been checked against the book.
  • NFPA-70-2020/Chapter 9/Table 9/AC Resistance Uncoated Copper Steel Conduit/8 AWG Unreviewed data: NEC 2020 Chapter 9, Table 9, AC Resistance Uncoated Copper Steel Conduit, 8 AWG (0.78 ohms per 1000 ft) has not been checked against the book.
  • NFPA-70-2020/Chapter 9/Table 9/XL Steel Conduit/8 AWG Unreviewed data: NEC 2020 Chapter 9, Table 9, XL Steel Conduit, 8 AWG (0.065 ohms per 1000 ft) has not been checked against the book.
  • NFPA-70-2020/Chapter 9/Table 9/AC Resistance Uncoated Copper Steel Conduit/14 AWG Unreviewed data: NEC 2020 Chapter 9, Table 9, AC Resistance Uncoated Copper Steel Conduit, 14 AWG (3.1 ohms per 1000 ft) has not been checked against the book.
  • NFPA-70-2020/Chapter 9/Table 9/XL Steel Conduit/14 AWG Unreviewed data: NEC 2020 Chapter 9, Table 9, XL Steel Conduit, 14 AWG (0.073 ohms per 1000 ft) has not been checked against the book.
  • NFPA-70-2020/Chapter 9/Table 9/AC Resistance Uncoated Copper Steel Conduit/12 AWG Unreviewed data: NEC 2020 Chapter 9, Table 9, AC Resistance Uncoated Copper Steel Conduit, 12 AWG (2.0 ohms per 1000 ft) has not been checked against the book.
  • NFPA-70-2020/Chapter 9/Table 9/XL Steel Conduit/12 AWG Unreviewed data: NEC 2020 Chapter 9, Table 9, XL Steel Conduit, 12 AWG (0.068 ohms per 1000 ft) has not been checked against the book.
  • NFPA-70-2020/Chapter 9/Table 9/AC Resistance Uncoated Copper Steel Conduit/10 AWG Unreviewed data: NEC 2020 Chapter 9, Table 9, AC Resistance Uncoated Copper Steel Conduit, 10 AWG (1.2 ohms per 1000 ft) has not been checked against the book.
  • NFPA-70-2020/Chapter 9/Table 9/XL Steel Conduit/10 AWG Unreviewed data: NEC 2020 Chapter 9, Table 9, XL Steel Conduit, 10 AWG (0.063 ohms per 1000 ft) has not been checked against the book.
  • NFPA-70-2020/Chapter 9/Table 9/AC Resistance Uncoated Copper Steel Conduit/6 AWG Unreviewed data: NEC 2020 Chapter 9, Table 9, AC Resistance Uncoated Copper Steel Conduit, 6 AWG (0.49 ohms per 1000 ft) has not been checked against the book.
  • NFPA-70-2020/Chapter 9/Table 9/XL Steel Conduit/6 AWG Unreviewed data: NEC 2020 Chapter 9, Table 9, XL Steel Conduit, 6 AWG (0.064 ohms per 1000 ft) has not been checked against the book.
  • NFPA-70-2020/Chapter 9/Table 9/AC Resistance Uncoated Copper Steel Conduit/4 AWG Unreviewed data: NEC 2020 Chapter 9, Table 9, AC Resistance Uncoated Copper Steel Conduit, 4 AWG (0.31 ohms per 1000 ft) has not been checked against the book.
  • NFPA-70-2020/Chapter 9/Table 9/XL Steel Conduit/4 AWG Unreviewed data: NEC 2020 Chapter 9, Table 9, XL Steel Conduit, 4 AWG (0.060 ohms per 1000 ft) has not been checked against the book.
  • NFPA-70-2020/Chapter 9/Table 9/AC Resistance Uncoated Copper Steel Conduit/2 AWG Unreviewed data: NEC 2020 Chapter 9, Table 9, AC Resistance Uncoated Copper Steel Conduit, 2 AWG (0.20 ohms per 1000 ft) has not been checked against the book.
  • NFPA-70-2020/Chapter 9/Table 9/XL Steel Conduit/2 AWG Unreviewed data: NEC 2020 Chapter 9, Table 9, XL Steel Conduit, 2 AWG (0.057 ohms per 1000 ft) has not been checked against the book.
  • NFPA-70-2020/Chapter 9/Table 9/AC Resistance Uncoated Copper Steel Conduit/1 AWG Unreviewed data: NEC 2020 Chapter 9, Table 9, AC Resistance Uncoated Copper Steel Conduit, 1 AWG (0.16 ohms per 1000 ft) has not been checked against the book.
  • NFPA-70-2020/Chapter 9/Table 9/XL Steel Conduit/1 AWG Unreviewed data: NEC 2020 Chapter 9, Table 9, XL Steel Conduit, 1 AWG (0.057 ohms per 1000 ft) has not been checked against the book.
  • NFPA-70-2020/Chapter 9/Table 9/AC Resistance Uncoated Copper Steel Conduit/1/0 AWG Unreviewed data: NEC 2020 Chapter 9, Table 9, AC Resistance Uncoated Copper Steel Conduit, 1/0 AWG (0.12 ohms per 1000 ft) has not been checked against the book.
  • NFPA-70-2020/Chapter 9/Table 9/XL Steel Conduit/1/0 AWG Unreviewed data: NEC 2020 Chapter 9, Table 9, XL Steel Conduit, 1/0 AWG (0.055 ohms per 1000 ft) has not been checked against the book.
  • NFPA-70-2020/Chapter 9/Table 9/AC Resistance Uncoated Copper Steel Conduit/2/0 AWG Unreviewed data: NEC 2020 Chapter 9, Table 9, AC Resistance Uncoated Copper Steel Conduit, 2/0 AWG (0.10 ohms per 1000 ft) has not been checked against the book.
  • NFPA-70-2020/Chapter 9/Table 9/XL Steel Conduit/2/0 AWG Unreviewed data: NEC 2020 Chapter 9, Table 9, XL Steel Conduit, 2/0 AWG (0.054 ohms per 1000 ft) has not been checked against the book.
  • NFPA-70-2020/Chapter 9/Table 9/AC Resistance Uncoated Copper Steel Conduit/3/0 AWG Unreviewed data: NEC 2020 Chapter 9, Table 9, AC Resistance Uncoated Copper Steel Conduit, 3/0 AWG (0.079 ohms per 1000 ft) has not been checked against the book.
  • NFPA-70-2020/Chapter 9/Table 9/XL Steel Conduit/3/0 AWG Unreviewed data: NEC 2020 Chapter 9, Table 9, XL Steel Conduit, 3/0 AWG (0.052 ohms per 1000 ft) has not been checked against the book.

Feeders

Scroll each table sideways for the drop, allowance and state columns.

EquipmentFed fromLength (ft)SizeDropAllowanceCumulative
SD-1DisconnectU-4--Bus0.00 %--Not countedabove the start point
KP-C1PanelSD-1504/0 AWG0.76 %Uses 2 unreviewed Table 9 values1.58 V2.00 %0.76 %Uses 2 unreviewed Table 9 valuesfrom SD-1
SD-2DisconnectU-4--Bus0.00 %--Not countedabove the start point
LP-C1PanelSD-2653 AWG1.39 %Uses 2 unreviewed Table 9 values2.89 V2.00 %1.39 %Uses 2 unreviewed Table 9 valuesfrom SD-2

Branch circuits

KP-C1

CktDescriptionLength (ft)CurrentSizeDropAllowanceMin sizeCombinedState
1,3,5Convection oven3040.00 A80 % of trip8 AWG0.78 %Uses 2 unreviewed Table 9 values1.63 V3.00 %12 AWGUses 26 unreviewed Table 9 values1.54 %Uses 4 unreviewed Table 9 valuesPass
2,4,6Commercial dishwasher4532.00 A80 % of trip8 AWG0.94 %Uses 2 unreviewed Table 9 values1.95 V3.00 %12 AWGUses 26 unreviewed Table 9 values1.70 %Uses 4 unreviewed Table 9 valuesPass
7,9Espresso machine5524.00 A80 % of trip10 AWG1.53 %Uses 2 unreviewed Table 9 values3.17 V3.00 %12 AWGUses 26 unreviewed Table 9 values2.28 %Uses 4 unreviewed Table 9 valuesPass
8,10Electric griddle3532.00 A80 % of trip8 AWG0.84 %Uses 2 unreviewed Table 9 values1.75 V3.00 %12 AWGUses 26 unreviewed Table 9 values1.60 %Uses 4 unreviewed Table 9 valuesPass
11Reach-in refrigerator4016.00 A80 % of trip12 AWG2.13 %Uses 2 unreviewed Table 9 values2.56 V3.00 %12 AWGUses 26 unreviewed Table 9 values2.89 %Uses 4 unreviewed Table 9 valuesPass
12Reach-in freezer4516.00 A80 % of trip12 AWG2.40 %Uses 2 unreviewed Table 9 values2.88 V3.00 %12 AWGUses 26 unreviewed Table 9 values3.16 %Uses 4 unreviewed Table 9 valuesPass
13Prep counter receptacles3016.00 A80 % of trip12 AWG1.60 %Uses 2 unreviewed Table 9 values1.92 V3.00 %14 AWGUses 26 unreviewed Table 9 values2.36 %Uses 4 unreviewed Table 9 valuesPass
14Ice machine5016.00 A80 % of trip12 AWG2.67 %Uses 2 unreviewed Table 9 values3.20 V3.00 %12 AWGUses 26 unreviewed Table 9 values3.43 %Uses 4 unreviewed Table 9 valuesPass
15Kitchen hood exhaust2516.00 A80 % of trip12 AWG1.33 %Uses 2 unreviewed Table 9 values1.60 V3.00 %14 AWGUses 26 unreviewed Table 9 values2.09 %Uses 4 unreviewed Table 9 valuesPass
16Coffee brewer5516.00 A80 % of trip12 AWG2.94 %Uses 2 unreviewed Table 9 values3.52 V3.00 %12 AWGUses 26 unreviewed Table 9 values3.69 %Uses 4 unreviewed Table 9 valuesPass
17,19,21Walk-in refrigeration6024.00 A80 % of trip10 AWG1.44 %Uses 2 unreviewed Table 9 values3.00 V3.00 %12 AWGUses 26 unreviewed Table 9 values2.20 %Uses 4 unreviewed Table 9 valuesPass
18,20,22Electric water heater2040.00 A80 % of trip8 AWG0.52 %Uses 2 unreviewed Table 9 values1.08 V3.00 %14 AWGUses 26 unreviewed Table 9 values1.28 %Uses 4 unreviewed Table 9 valuesPass

LP-C1

CktDescriptionLength (ft)CurrentSizeDropAllowanceMin sizeCombinedState
1Dining pendant lighting6016.00 A80 % of trip10 AWG1.92 %Uses 2 unreviewed Table 9 values2.31 V3.00 %10 AWGUses 24 unreviewed Table 9 values3.31 %Uses 4 unreviewed Table 9 valuesPass
2Kitchen and service lighting4516.00 A80 % of trip12 AWG2.40 %Uses 2 unreviewed Table 9 values2.88 V3.00 %12 AWGUses 26 unreviewed Table 9 values3.79 %Uses 4 unreviewed Table 9 valuesPass
3Dining receptacles - east7016.00 A80 % of trip10 AWG2.24 %Uses 2 unreviewed Table 9 values2.69 V3.00 %10 AWGUses 24 unreviewed Table 9 values3.63 %Uses 4 unreviewed Table 9 valuesPass
4Dining receptacles - west8016.00 A80 % of trip10 AWG2.56 %Uses 2 unreviewed Table 9 values3.08 V3.00 %10 AWGUses 24 unreviewed Table 9 values3.95 %Uses 4 unreviewed Table 9 valuesPass
5POS and network equipment4016.00 A80 % of trip12 AWG2.13 %Uses 2 unreviewed Table 9 values2.56 V3.00 %12 AWGUses 26 unreviewed Table 9 values3.52 %Uses 4 unreviewed Table 9 valuesPass
6Exterior sign and entry lighting9016.00 A80 % of trip10 AWG2.88 %Uses 2 unreviewed Table 9 values3.46 V3.00 %10 AWGUses 24 unreviewed Table 9 values4.27 %Uses 4 unreviewed Table 9 valuesPass
7,9,11Rooftop HVAC unit7524.00 A80 % of trip10 AWG1.80 %Uses 2 unreviewed Table 9 values3.75 V3.00 %12 AWGUses 26 unreviewed Table 9 values3.19 %Uses 4 unreviewed Table 9 valuesPass
8Restroom receptacles5016.00 A80 % of trip12 AWG2.67 %Uses 2 unreviewed Table 9 values3.20 V3.00 %12 AWGUses 26 unreviewed Table 9 values4.06 %Uses 4 unreviewed Table 9 valuesPass
10Patio receptacles8516.00 A80 % of trip10 AWG2.72 %Uses 2 unreviewed Table 9 values3.27 V3.00 %10 AWGUses 24 unreviewed Table 9 values4.11 %Uses 4 unreviewed Table 9 valuesPass
12Office receptacles3516.00 A80 % of trip12 AWG1.87 %Uses 2 unreviewed Table 9 values2.24 V3.00 %14 AWGUses 26 unreviewed Table 9 values3.26 %Uses 4 unreviewed Table 9 valuesPass