LP-C1 (FRONT-OF-HOUSE STORAGE)
LP-C1
MAIN:M.C.B.RATING:100 ASPACES:30SERVICE: 120/208 V, 3-PHASE, 4-WIREMOUNTING: SURFACEFEEDS FROM: BUILDING DISTRIBUTION / 100 A FEEDERPANEL SCCR: 10 KATRIM: HINGED DOOR, NEMA 1A.I.C.: 10 KAFAULT CURRENT CALCULATED 2026-11-22 / fnv1a32:a890e64cAFC: 6.1 KA, uses Eaton Table 4 C values not yet checked against the bookA.I.C. PASS, SCCR PASS| CKT | DESCRIPTION | KVA | CIRCUIT BREAKER | BRANCH CIRCUIT | C | VD% | PH | CKT | DESCRIPTION | KVA | CIRCUIT BREAKER | BRANCH CIRCUIT | C | VD% | PH | ||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| POLE | TRIP | P | N | GND | POLE | TRIP | P | N | GND | ||||||||||||
| 1 | 1.08 | 1 | 20 | 10 | 10 | 10 | -- | 1.92 | A | 2 | 1.2 | 1 | 20 | 12 | 12 | 12 | -- | 2.40 | A | ||
| 3 | 1.44 | 1 | 20 | 10 | 10 | 10 | -- | 2.24 | B | 4 | 1.44 | 1 | 20 | 10 | 10 | 10 | -- | 2.56 | B | ||
| 5 | 0.72 | 1 | 20 | 12 | 12 | 12 | -- | 2.13 | C | 6 | 0.6 | 1 | 20 | 10 | 10 | 10 | -- | 2.88 | C | ||
| 7 | 7.5 | 3 | 30 | 10 | -- | 10 | -- | 1.80 | A | 8 | 1.2 | 1 | 20 | 12 | 12 | 12 | -- | 2.67 | A | ||
| 9 | 10 | -- | -- | B | 10 | 1.08 | 1 | 20 | 10 | 10 | 10 | -- | 2.72 | B | |||||||
| 11 | 10 | -- | -- | C | 12 | 1.08 | 1 | 20 | 12 | 12 | 12 | -- | 1.87 | C | |||||||
| 13 | -- | -- | -- | -- | -- | -- | -- | -- | A | 14 | -- | -- | -- | -- | -- | -- | -- | -- | A | ||
| 15 | -- | 1 | 20 | -- | -- | -- | -- | -- | B | 16 | -- | 1 | 20 | -- | -- | -- | -- | -- | B | ||
| 17 | -- | -- | -- | -- | -- | -- | -- | -- | C | 18 | -- | -- | -- | -- | -- | -- | -- | -- | C | ||
| 19 | -- | -- | -- | -- | -- | -- | -- | -- | A | 20 | -- | -- | -- | -- | -- | -- | -- | -- | A | ||
| 21 | -- | -- | -- | -- | -- | -- | -- | -- | B | 22 | -- | -- | -- | -- | -- | -- | -- | -- | B | ||
| 23 | -- | -- | -- | -- | -- | -- | -- | -- | C | 24 | -- | -- | -- | -- | -- | -- | -- | -- | C | ||
| 25 | -- | -- | -- | -- | -- | -- | -- | -- | A | 26 | -- | -- | -- | -- | -- | -- | -- | -- | A | ||
| 27 | -- | -- | -- | -- | -- | -- | -- | -- | B | 28 | -- | -- | -- | -- | -- | -- | -- | -- | B | ||
| 29 | -- | -- | -- | -- | -- | -- | -- | -- | C | 30 | -- | -- | -- | -- | -- | -- | -- | -- | C | ||
CONNECTED LOAD: 17.34 KVAPHASE A: 49.8 APHASE B: 53.8 APHASE C: 40.8 AIMBALANCE: 27.0% | |||||||||||||||||||||
WORST COMBINED VOLTAGE DROP: 4.27% AT CKT 6, C405.5.3, uses Table 9 values not yet checked against the book | |||||||||||||||||||||
CALCULATED LOAD: 20.41 KVA (20.74 KVA CONTINUOUS AT 125%)MAXIMUM LOAD: 65.00 A, 65% OF 100 A MAIN, HEAVIEST LINE ACONTINUOUS AT 125%: 65.00 A, 65% OF 100 A MAIN, HEAVIEST LINE A | |||||||||||||||||||||
GENERAL LIGHTINGCOUNTED 2.28 KVADEMAND 3.60 KVATable 220.12 unit load or 125 % of connected, whichever is larger, then Table 220.42 | |||||||||||||||||||||
RECEPTACLESCOUNTED 6.12 KVADEMAND 6.12 KVATable 220.44: first 10 kVA at 100 %, the rest at 50 % | |||||||||||||||||||||
MOTORCOUNTED 7.49 KVADEMAND 9.37 KVA220.50 and 430.24: every motor plus 25 % of the largest | |||||||||||||||||||||
OTHER (NAMEPLATE)COUNTED 1.32 KVADEMAND 1.32 KVA220.14(A): nameplate at 100 % | |||||||||||||||||||||
| Unreviewed data: the calculated load uses NEC 2020 values not yet checked against the book: Table 220.12 (Restaurant); Table 220.42 (All others, total factor); 220.14(I) (single or multiple receptacle on one yoke); Table 220.44 (first band limit, first band factor, remainder factor). | |||||||||||||||||||||
| NOTES: Synthetic demonstration schedule. Connected loads, run lengths, raceways, installed conductor sizes, load categories, served areas, equipment ratings, energy code scope and fault-current inputs are fictional. Table values are not yet checked against the book. | |||||||||||||||||||||
| Unreviewed data: 1 C value from Eaton's Short-Circuit Current Calculations (2014), Table 4, three single conductors at 600 V, used on the run to LP-C1, not yet checked against the bulletin: copper in steel conduit: 3 AWG. get_fault_current lists each value and where it is used. | |||||||||||||||||||||
Calculated load
Calculated20.41 kVA20.74 kVA with continuous loads at 125 %
- Maximum load
- 65.00 A 65 % of the 100 A mainheaviest line A
- Continuous at 125 %
- 65.00 A 65 % of the 100 A mainheaviest line A
At 208 V, three-phase.
| Category | Counted | Demand | Rule |
|---|---|---|---|
| General lighting | 2.28 kVA | 3.60 kVA | Table 220.12 unit load or 125 % of connected, whichever is larger, then Table 220.42 |
| Receptacles | 6.12 kVA | 6.12 kVA | Table 220.44: first 10 kVA at 100 %, the rest at 50 % |
| Motor | 7.49 kVA | 9.37 kVA | 220.50 and 430.24: every motor plus 25 % of the largest |
| Other (nameplate) | 1.32 kVA | 1.32 kVA | 220.14(A): nameplate at 100 % |
- Unreviewed data: 6 table values (Table 220.12, Table 220.42, 220.14(I), Table 220.44) not yet checked against the code book.