KP-C1 (KITCHEN SERVICE CORRIDOR)
KP-C1
MAIN:M.C.B.RATING:225 ASPACES:42SERVICE: 120/208 V, 3-PHASE, 4-WIREMOUNTING: SURFACEFEEDS FROM: BUILDING DISTRIBUTION / 225 A FEEDERPANEL SCCR: 22 KATRIM: HINGED DOOR, NEMA 1A.I.C.: 22 KAFAULT CURRENT CALCULATED 2026-11-22 / fnv1a32:a890e64cAFC: 12.2 KA, uses Eaton Table 4 C values not yet checked against the bookA.I.C. PASS, SCCR PASS
Panel schedule for KP-C1, odd circuits on the left and even circuits on the right
CKTDESCRIPTIONKVACIRCUIT BREAKERBRANCH CIRCUITCVD%PHCKTDESCRIPTIONKVACIRCUIT BREAKERBRANCH CIRCUITCVD%PH
POLETRIPPNGNDPOLETRIPPNGND
112.03508--10--0.78A29.03408--10--0.94A
38----B48----B
58----C68----C
74.523010--10--1.53A86.02408--10--0.84A
910----B108----B
110.96120121212--2.13C121.2120121212--2.40C
131.8120121212--1.60A141.44120121212--2.67A
151.2120121212--1.33B161.8120121212--2.94B
174.533010--10--1.44C1812.03508--10--0.52C
1910----A208----A
2110----B228----B
23----------------C24----------------C
25--120----------A26--120----------A
27----------------B28----------------B
29----------------C30----------------C
31----------------A32----------------A
33----------------B34----------------B
35----------------C36----------------C
37----------------A38----------------A
39----------------B40----------------B
41----------------C42----------------C
CONNECTED LOAD: 56.4 KVAPHASE A: 174.9 APHASE B: 172.9 APHASE C: 122.2 AIMBALANCE: 33.7%
WORST COMBINED VOLTAGE DROP: 3.69% AT CKT 16, C405.5.3, uses Table 9 values not yet checked against the book
CALCULATED LOAD: 41.67 KVA (41.67 KVA CONTINUOUS AT 125%)MAXIMUM LOAD: 131.61 A, 58% OF 225 A MAIN, HEAVIEST LINE ACONTINUOUS AT 125%: 131.61 A, 58% OF 225 A MAIN, HEAVIEST LINE A
RECEPTACLESCOUNTED 1.80 KVADEMAND 1.80 KVATable 220.44: first 10 kVA at 100 %, the rest at 50 %
MOTORCOUNTED 5.70 KVADEMAND 6.83 KVA220.50 and 430.24: every motor plus 25 % of the largest
KITCHEN EQUIPMENTCOUNTED 45.30 KVADEMAND 29.45 KVATable 220.56: 6 units at 65 %, not less than the two largest
OTHER (NAMEPLATE)COUNTED 3.60 KVADEMAND 3.60 KVA220.14(A): nameplate at 100 %
Unreviewed data: the calculated load uses NEC 2020 values not yet checked against the book: 220.14(I) (single or multiple receptacle on one yoke); Table 220.44 (first band limit, first band factor, remainder factor); Table 220.56 (6 and over units).
NOTES: Synthetic demonstration schedule. Connected loads, run lengths, raceways, installed conductor sizes, load categories, served areas, equipment ratings, energy code scope and fault-current inputs are fictional. Table values are not yet checked against the book.
Unreviewed data: 1 C value from Eaton's Short-Circuit Current Calculations (2014), Table 4, three single conductors at 600 V, used on the run to KP-C1, not yet checked against the bulletin: copper in steel conduit: 4/0 AWG. get_fault_current lists each value and where it is used.

Calculated load

Calculated

41.67 kVA41.67 kVA with continuous loads at 125 %

Maximum load
131.61 A 58 % of the 225 A mainheaviest line A
Continuous at 125 %
131.61 A 58 % of the 225 A mainheaviest line A

At 208 V, three-phase.

Calculated load by category
CategoryCountedDemandRule
Receptacles1.80 kVA1.80 kVATable 220.44: first 10 kVA at 100 %, the rest at 50 %
Motor5.70 kVA6.83 kVA220.50 and 430.24: every motor plus 25 % of the largest
Kitchen equipment45.30 kVA29.45 kVATable 220.56: 6 units at 65 %, not less than the two largest
Other (nameplate)3.60 kVA3.60 kVA220.14(A): nameplate at 100 %
  • Unreviewed data: 5 table values (220.14(I), Table 220.44, Table 220.56) not yet checked against the code book.