KP-C1 (KITCHEN SERVICE CORRIDOR)
KP-C1
MAIN:M.C.B.RATING:225 ASPACES:42SERVICE: 120/208 V, 3-PHASE, 4-WIREMOUNTING: SURFACEFEEDS FROM: BUILDING DISTRIBUTION / 225 A FEEDERPANEL SCCR: 22 KATRIM: HINGED DOOR, NEMA 1A.I.C.: 22 KAFAULT CURRENT CALCULATED 2026-11-22 / fnv1a32:a890e64cAFC: 12.2 KA, uses Eaton Table 4 C values not yet checked against the bookA.I.C. PASS, SCCR PASS| CKT | DESCRIPTION | KVA | CIRCUIT BREAKER | BRANCH CIRCUIT | C | VD% | PH | CKT | DESCRIPTION | KVA | CIRCUIT BREAKER | BRANCH CIRCUIT | C | VD% | PH | ||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| POLE | TRIP | P | N | GND | POLE | TRIP | P | N | GND | ||||||||||||
| 1 | 12.0 | 3 | 50 | 8 | -- | 10 | -- | 0.78 | A | 2 | 9.0 | 3 | 40 | 8 | -- | 10 | -- | 0.94 | A | ||
| 3 | 8 | -- | -- | B | 4 | 8 | -- | -- | B | ||||||||||||
| 5 | 8 | -- | -- | C | 6 | 8 | -- | -- | C | ||||||||||||
| 7 | 4.5 | 2 | 30 | 10 | -- | 10 | -- | 1.53 | A | 8 | 6.0 | 2 | 40 | 8 | -- | 10 | -- | 0.84 | A | ||
| 9 | 10 | -- | -- | B | 10 | 8 | -- | -- | B | ||||||||||||
| 11 | 0.96 | 1 | 20 | 12 | 12 | 12 | -- | 2.13 | C | 12 | 1.2 | 1 | 20 | 12 | 12 | 12 | -- | 2.40 | C | ||
| 13 | 1.8 | 1 | 20 | 12 | 12 | 12 | -- | 1.60 | A | 14 | 1.44 | 1 | 20 | 12 | 12 | 12 | -- | 2.67 | A | ||
| 15 | 1.2 | 1 | 20 | 12 | 12 | 12 | -- | 1.33 | B | 16 | 1.8 | 1 | 20 | 12 | 12 | 12 | -- | 2.94 | B | ||
| 17 | 4.5 | 3 | 30 | 10 | -- | 10 | -- | 1.44 | C | 18 | 12.0 | 3 | 50 | 8 | -- | 10 | -- | 0.52 | C | ||
| 19 | 10 | -- | -- | A | 20 | 8 | -- | -- | A | ||||||||||||
| 21 | 10 | -- | -- | B | 22 | 8 | -- | -- | B | ||||||||||||
| 23 | -- | -- | -- | -- | -- | -- | -- | -- | C | 24 | -- | -- | -- | -- | -- | -- | -- | -- | C | ||
| 25 | -- | 1 | 20 | -- | -- | -- | -- | -- | A | 26 | -- | 1 | 20 | -- | -- | -- | -- | -- | A | ||
| 27 | -- | -- | -- | -- | -- | -- | -- | -- | B | 28 | -- | -- | -- | -- | -- | -- | -- | -- | B | ||
| 29 | -- | -- | -- | -- | -- | -- | -- | -- | C | 30 | -- | -- | -- | -- | -- | -- | -- | -- | C | ||
| 31 | -- | -- | -- | -- | -- | -- | -- | -- | A | 32 | -- | -- | -- | -- | -- | -- | -- | -- | A | ||
| 33 | -- | -- | -- | -- | -- | -- | -- | -- | B | 34 | -- | -- | -- | -- | -- | -- | -- | -- | B | ||
| 35 | -- | -- | -- | -- | -- | -- | -- | -- | C | 36 | -- | -- | -- | -- | -- | -- | -- | -- | C | ||
| 37 | -- | -- | -- | -- | -- | -- | -- | -- | A | 38 | -- | -- | -- | -- | -- | -- | -- | -- | A | ||
| 39 | -- | -- | -- | -- | -- | -- | -- | -- | B | 40 | -- | -- | -- | -- | -- | -- | -- | -- | B | ||
| 41 | -- | -- | -- | -- | -- | -- | -- | -- | C | 42 | -- | -- | -- | -- | -- | -- | -- | -- | C | ||
CONNECTED LOAD: 56.4 KVAPHASE A: 174.9 APHASE B: 172.9 APHASE C: 122.2 AIMBALANCE: 33.7% | |||||||||||||||||||||
WORST COMBINED VOLTAGE DROP: 3.69% AT CKT 16, C405.5.3, uses Table 9 values not yet checked against the book | |||||||||||||||||||||
CALCULATED LOAD: 41.67 KVA (41.67 KVA CONTINUOUS AT 125%)MAXIMUM LOAD: 131.61 A, 58% OF 225 A MAIN, HEAVIEST LINE ACONTINUOUS AT 125%: 131.61 A, 58% OF 225 A MAIN, HEAVIEST LINE A | |||||||||||||||||||||
RECEPTACLESCOUNTED 1.80 KVADEMAND 1.80 KVATable 220.44: first 10 kVA at 100 %, the rest at 50 % | |||||||||||||||||||||
MOTORCOUNTED 5.70 KVADEMAND 6.83 KVA220.50 and 430.24: every motor plus 25 % of the largest | |||||||||||||||||||||
KITCHEN EQUIPMENTCOUNTED 45.30 KVADEMAND 29.45 KVATable 220.56: 6 units at 65 %, not less than the two largest | |||||||||||||||||||||
OTHER (NAMEPLATE)COUNTED 3.60 KVADEMAND 3.60 KVA220.14(A): nameplate at 100 % | |||||||||||||||||||||
| Unreviewed data: the calculated load uses NEC 2020 values not yet checked against the book: 220.14(I) (single or multiple receptacle on one yoke); Table 220.44 (first band limit, first band factor, remainder factor); Table 220.56 (6 and over units). | |||||||||||||||||||||
| NOTES: Synthetic demonstration schedule. Connected loads, run lengths, raceways, installed conductor sizes, load categories, served areas, equipment ratings, energy code scope and fault-current inputs are fictional. Table values are not yet checked against the book. | |||||||||||||||||||||
| Unreviewed data: 1 C value from Eaton's Short-Circuit Current Calculations (2014), Table 4, three single conductors at 600 V, used on the run to KP-C1, not yet checked against the bulletin: copper in steel conduit: 4/0 AWG. get_fault_current lists each value and where it is used. | |||||||||||||||||||||
Calculated load
Calculated41.67 kVA41.67 kVA with continuous loads at 125 %
- Maximum load
- 131.61 A 58 % of the 225 A mainheaviest line A
- Continuous at 125 %
- 131.61 A 58 % of the 225 A mainheaviest line A
At 208 V, three-phase.
| Category | Counted | Demand | Rule |
|---|---|---|---|
| Receptacles | 1.80 kVA | 1.80 kVA | Table 220.44: first 10 kVA at 100 %, the rest at 50 % |
| Motor | 5.70 kVA | 6.83 kVA | 220.50 and 430.24: every motor plus 25 % of the largest |
| Kitchen equipment | 45.30 kVA | 29.45 kVA | Table 220.56: 6 units at 65 %, not less than the two largest |
| Other (nameplate) | 3.60 kVA | 3.60 kVA | 220.14(A): nameplate at 100 % |
- Unreviewed data: 5 table values (220.14(I), Table 220.44, Table 220.56) not yet checked against the code book.