SD-1 Disconnect Unreviewed data
56,403 41,674 (uses unreviewed table data) 131.61 131.61 131.61 (line A) 208 V 3-ph Calculated The figures below use 5 NEC 220
values not yet checked against the
code book, listed at the end.
Category breakdown Category Connected VA Demand VA Continuous at 125 % Rule ReceptaclesTable 220.44: first 10 kVA at 100 %, the rest at 50 % 1,800 1,800 1,800 Table 220.44: first 10 kVA at 100 %, the rest at 50 % Motor220.50 and 430.24: every motor plus 25 % of the largest 5,703 6,829 6,829 220.50 and 430.24: every motor plus 25 % of the largest Kitchen equipmentTable 220.56: 6 units at 65 %, not less than the two largest 45,300 29,445 29,445 Table 220.56: 6 units at 65 %, not less than the two largest Other (nameplate)220.14(A): nameplate at 100 % 3,600 3,600 3,600 220.14(A): nameplate at 100 %
Noncoincident loads (220.60) No noncoincident groups below this node.
Currents At 208 V, 3-phase, 3 poles, from the supply that feeds it.
Maximum load 131.61 A Balanced 115.68 A; heaviest line 131.61 (line A). The heaviest line governs.
Continuous at 125 % 131.61 A Balanced 115.68 A; heaviest line 131.61 (line A). The heaviest line governs.
Unreviewed NEC 220 values (5) Transcribed from secondary sources and not yet checked against NFPA 70
(2020). They compute.
220.14(I), single or multiple receptacle on one yoke uses 180 VA per yoke Table 220.44, first band limit uses 10000 VA Table 220.44, first band factor uses 1 (demand factor) Table 220.44, remainder factor uses 0.5 (demand factor) Table 220.56, 6 and over units uses 0.65 (demand factor) KP-C1 Panel Unreviewed data
56,403 41,674 (uses unreviewed table data) 131.61 131.61 131.61 (line A) 208 V 3-ph Calculated The figures below use 5 NEC 220
values not yet checked against the
code book, listed at the end.
Category breakdown Category Connected VA Demand VA Continuous at 125 % Rule ReceptaclesTable 220.44: first 10 kVA at 100 %, the rest at 50 % 1,800 1,800 1,800 Table 220.44: first 10 kVA at 100 %, the rest at 50 % Motor220.50 and 430.24: every motor plus 25 % of the largest 5,703 6,829 6,829 220.50 and 430.24: every motor plus 25 % of the largest Kitchen equipmentTable 220.56: 6 units at 65 %, not less than the two largest 45,300 29,445 29,445 Table 220.56: 6 units at 65 %, not less than the two largest Other (nameplate)220.14(A): nameplate at 100 % 3,600 3,600 3,600 220.14(A): nameplate at 100 %
Noncoincident loads (220.60) No noncoincident groups below this node.
Currents At 208 V, 3-phase, 3 poles, from the supply that feeds it.
Maximum load 131.61 A Balanced 115.68 A; heaviest line 131.61 (line A). The heaviest line governs.
Continuous at 125 % 131.61 A Balanced 115.68 A; heaviest line 131.61 (line A). The heaviest line governs.
Unreviewed NEC 220 values (5) Transcribed from secondary sources and not yet checked against NFPA 70
(2020). They compute.
220.14(I), single or multiple receptacle on one yoke uses 180 VA per yoke Table 220.44, first band limit uses 10000 VA Table 220.44, first band factor uses 1 (demand factor) Table 220.44, remainder factor uses 0.5 (demand factor) Table 220.56, 6 and over units uses 0.65 (demand factor) Open KP-C1 in the panel editor
SD-2 Disconnect Unreviewed data
17,214 20,407 (uses unreviewed table data) 65.00 65.00 65.00 (line A) 208 V 3-ph Calculated The figures below use 6 NEC 220
values not yet checked against the
code book, listed at the end.
Category breakdown Category Connected VA Demand VA Continuous at 125 % Rule General lightingTable 220.12 unit load or 125 % of connected, whichever is larger, then Table 220.42 2,280 3,600 3,600 Table 220.12 unit load or 125 % of connected, whichever is larger, then Table 220.42 ReceptaclesTable 220.44: first 10 kVA at 100 %, the rest at 50 % 6,120 6,120 6,120 Table 220.44: first 10 kVA at 100 %, the rest at 50 % Motor220.50 and 430.24: every motor plus 25 % of the largest 7,494 9,367 9,367 220.50 and 430.24: every motor plus 25 % of the largest Other (nameplate)220.14(A): nameplate at 100 % 1,320 1,320 1,650 220.14(A): nameplate at 100 %
Noncoincident loads (220.60) No noncoincident groups below this node.
Currents At 208 V, 3-phase, 3 poles, from the supply that feeds it.
Maximum load 65.00 A Balanced 56.64 A; heaviest line 65.00 (line A). The heaviest line governs.
Continuous at 125 % 65.00 A Balanced 57.56 A; heaviest line 65.00 (line A). The heaviest line governs.
Unreviewed NEC 220 values (6) Transcribed from secondary sources and not yet checked against NFPA 70
(2020). They compute.
Table 220.12, Restaurant uses 1.5 VA/ft² Table 220.42, All others, total factor uses 1 (demand factor) 220.14(I), single or multiple receptacle on one yoke uses 180 VA per yoke Table 220.44, first band limit uses 10000 VA Table 220.44, first band factor uses 1 (demand factor) Table 220.44, remainder factor uses 0.5 (demand factor) LP-C1 Panel Unreviewed data
17,214 20,407 (uses unreviewed table data) 65.00 65.00 65.00 (line A) 208 V 3-ph Calculated The figures below use 6 NEC 220
values not yet checked against the
code book, listed at the end.
Category breakdown Category Connected VA Demand VA Continuous at 125 % Rule General lightingTable 220.12 unit load or 125 % of connected, whichever is larger, then Table 220.42 2,280 3,600 3,600 Table 220.12 unit load or 125 % of connected, whichever is larger, then Table 220.42 ReceptaclesTable 220.44: first 10 kVA at 100 %, the rest at 50 % 6,120 6,120 6,120 Table 220.44: first 10 kVA at 100 %, the rest at 50 % Motor220.50 and 430.24: every motor plus 25 % of the largest 7,494 9,367 9,367 220.50 and 430.24: every motor plus 25 % of the largest Other (nameplate)220.14(A): nameplate at 100 % 1,320 1,320 1,650 220.14(A): nameplate at 100 %
Noncoincident loads (220.60) No noncoincident groups below this node.
Currents At 208 V, 3-phase, 3 poles, from the supply that feeds it.
Maximum load 65.00 A Balanced 56.64 A; heaviest line 65.00 (line A). The heaviest line governs.
Continuous at 125 % 65.00 A Balanced 57.56 A; heaviest line 65.00 (line A). The heaviest line governs.
Unreviewed NEC 220 values (6) Transcribed from secondary sources and not yet checked against NFPA 70
(2020). They compute.
Table 220.12, Restaurant uses 1.5 VA/ft² Table 220.42, All others, total factor uses 1 (demand factor) 220.14(I), single or multiple receptacle on one yoke uses 180 VA per yoke Table 220.44, first band limit uses 10000 VA Table 220.44, first band factor uses 1 (demand factor) Table 220.44, remainder factor uses 0.5 (demand factor) Open LP-C1 in the panel editor