DEMO - Meadow Commons Cafe

DEMO-26004Cafe and commercial kitchen404 Meadow Walk, Example City - fictional siteConstruction administrationCommercial energy code

Fictional 2,400 sf neighborhood cafe with 48 seats, electric cooking, espresso service and walk-in refrigeration. Demonstration data only; no real client, person or address is represented.

NEC 2020 Article 220 calculated loads for non-dwelling occupancies, from the linked feeder tree each time the page loads.

Service

Disconnect SD-1

Calculated
Calculated load
41,674 VA (uses unreviewed table data)
Continuous at 125 %
41,674 VA
Maximum-load current
131.61 A
Continuous-adjusted current
131.61 A
Supply
208 V, 3-phase

Every figure here uses NEC 220 table values not yet checked against the code book.

Disconnect SD-2

Calculated
Calculated load
20,407 VA (uses unreviewed table data)
Continuous at 125 %
20,737 VA
Maximum-load current
65.00 A
Continuous-adjusted current
65.00 A
Supply
208 V, 3-phase

Every figure here uses NEC 220 table values not yet checked against the code book.

By equipment

4 results use NEC 220 table values not yet checked against the code book. They compute; open a row to see which.

EquipmentConnected VACalculated VAMax load AContinuous AHeaviest line ASupplyState

Unreviewed data

56,40341,674 (uses unreviewed table data)131.61131.61131.61 (line A)208 V 3-phCalculated

Unreviewed data

56,40341,674 (uses unreviewed table data)131.61131.61131.61 (line A)208 V 3-phCalculated

Unreviewed data

17,21420,407 (uses unreviewed table data)65.0065.0065.00 (line A)208 V 3-phCalculated

Unreviewed data

17,21420,407 (uses unreviewed table data)65.0065.0065.00 (line A)208 V 3-phCalculated