M-3 Meter Unreviewed data
34,836 39,600 (uses unreviewed table data) 129.51 141.96 129.51 (line A) 208 V 3-ph Calculated The figures below use 7 NEC 220
values not yet checked against the
code book, listed at the end.
Category breakdown Category Connected VA Demand VA Continuous at 125 % Rule General lightingTable 220.12 unit load or 125 % of connected, whichever is larger, then Table 220.42 4,800 11,050 11,050 Table 220.12 unit load or 125 % of connected, whichever is larger, then Table 220.42 ReceptaclesTable 220.44: first 10 kVA at 100 %, the rest at 50 %, with the 220.14(K) office minimum 14,220 12,110 12,110 Table 220.44: first 10 kVA at 100 %, the rest at 50 %, with the 220.14(K) office minimum Motor220.50 and 430.24: every motor plus 25 % of the largest 2,496 3,120 3,120 220.50 and 430.24: every motor plus 25 % of the largest Other (nameplate)220.14(A): nameplate at 100 % 13,320 13,320 15,345 220.14(A): nameplate at 100 %
Noncoincident loads (220.60) No noncoincident groups below this node.
Currents At 208 V, 3-phase, 3 poles, from the supply that feeds it.
Maximum load 129.51 A Balanced 109.92 A; heaviest line 129.51 (line A). The heaviest line governs.
Continuous at 125 % 141.96 A Balanced 115.54 A; heaviest line 141.96 (line A). The heaviest line governs.
Unreviewed NEC 220 values (7) Transcribed from secondary sources and not yet checked against NFPA 70
(2020). They compute.
Table 220.12, Office uses 1.3 VA/ft² Table 220.42, All others, total factor uses 1 (demand factor) 220.14(I), single or multiple receptacle on one yoke uses 180 VA per yoke Table 220.44, first band limit uses 10000 VA Table 220.44, first band factor uses 1 (demand factor) Table 220.44, remainder factor uses 0.5 (demand factor) 220.14(K), office receptacle minimum uses 1 VA/ft² SD-1 Disconnect Unreviewed data
17,760 23,430 (uses unreviewed table data) 74.48 74.48 74.48 (line C) 208 V 3-ph Calculated The figures below use 7 NEC 220
values not yet checked against the
code book, listed at the end.
Category breakdown Category Connected VA Demand VA Continuous at 125 % Rule General lightingTable 220.12 unit load or 125 % of connected, whichever is larger, then Table 220.42 4,800 11,050 11,050 Table 220.12 unit load or 125 % of connected, whichever is larger, then Table 220.42 ReceptaclesTable 220.44: first 10 kVA at 100 %, the rest at 50 %, with the 220.14(K) office minimum 11,160 10,580 10,580 Table 220.44: first 10 kVA at 100 %, the rest at 50 %, with the 220.14(K) office minimum Other (nameplate)220.14(A): nameplate at 100 % 1,800 1,800 1,800 220.14(A): nameplate at 100 %
Noncoincident loads (220.60) No noncoincident groups below this node.
Currents At 208 V, 3-phase, 3 poles, from the supply that feeds it.
Maximum load 74.48 A Balanced 65.04 A; heaviest line 74.48 (line C). The heaviest line governs.
Continuous at 125 % 74.48 A Balanced 65.04 A; heaviest line 74.48 (line C). The heaviest line governs.
Unreviewed NEC 220 values (7) Transcribed from secondary sources and not yet checked against NFPA 70
(2020). They compute.
Table 220.12, Office uses 1.3 VA/ft² Table 220.42, All others, total factor uses 1 (demand factor) 220.14(I), single or multiple receptacle on one yoke uses 180 VA per yoke Table 220.44, first band limit uses 10000 VA Table 220.44, first band factor uses 1 (demand factor) Table 220.44, remainder factor uses 0.5 (demand factor) 220.14(K), office receptacle minimum uses 1 VA/ft² LP-O1 Panel Unreviewed data
17,760 23,430 (uses unreviewed table data) 74.48 74.48 74.48 (line C) 208 V 3-ph Calculated The figures below use 7 NEC 220
values not yet checked against the
code book, listed at the end.
Category breakdown Category Connected VA Demand VA Continuous at 125 % Rule General lightingTable 220.12 unit load or 125 % of connected, whichever is larger, then Table 220.42 4,800 11,050 11,050 Table 220.12 unit load or 125 % of connected, whichever is larger, then Table 220.42 ReceptaclesTable 220.44: first 10 kVA at 100 %, the rest at 50 %, with the 220.14(K) office minimum 11,160 10,580 10,580 Table 220.44: first 10 kVA at 100 %, the rest at 50 %, with the 220.14(K) office minimum Other (nameplate)220.14(A): nameplate at 100 % 1,800 1,800 1,800 220.14(A): nameplate at 100 %
Noncoincident loads (220.60) No noncoincident groups below this node.
Currents At 208 V, 3-phase, 3 poles, from the supply that feeds it.
Maximum load 74.48 A Balanced 65.04 A; heaviest line 74.48 (line C). The heaviest line governs.
Continuous at 125 % 74.48 A Balanced 65.04 A; heaviest line 74.48 (line C). The heaviest line governs.
Unreviewed NEC 220 values (7) Transcribed from secondary sources and not yet checked against NFPA 70
(2020). They compute.
Table 220.12, Office uses 1.3 VA/ft² Table 220.42, All others, total factor uses 1 (demand factor) 220.14(I), single or multiple receptacle on one yoke uses 180 VA per yoke Table 220.44, first band limit uses 10000 VA Table 220.44, first band factor uses 1 (demand factor) Table 220.44, remainder factor uses 0.5 (demand factor) 220.14(K), office receptacle minimum uses 1 VA/ft² Open LP-O1 in the panel editor
SD-2 Disconnect Unreviewed data
17,076 23,140 (uses unreviewed table data) 80.83 80.83 80.83 (line C) 208 V 3-ph Calculated The figures below use 5 NEC 220
values not yet checked against the
code book, listed at the end.
Category breakdown Category Connected VA Demand VA Continuous at 125 % Rule ReceptaclesTable 220.44: first 10 kVA at 100 %, the rest at 50 %, with the 220.14(K) office minimum 3,060 8,500 8,500 Table 220.44: first 10 kVA at 100 %, the rest at 50 %, with the 220.14(K) office minimum Motor220.50 and 430.24: every motor plus 25 % of the largest 2,496 3,120 3,120 220.50 and 430.24: every motor plus 25 % of the largest Other (nameplate)220.14(A): nameplate at 100 % 11,520 11,520 13,545 220.14(A): nameplate at 100 %
Noncoincident loads (220.60) No noncoincident groups below this node.
Currents At 208 V, 3-phase, 3 poles, from the supply that feeds it.
Maximum load 80.83 A Balanced 64.23 A; heaviest line 80.83 (line C). The heaviest line governs.
Continuous at 125 % 80.83 A Balanced 69.85 A; heaviest line 80.83 (line C). The heaviest line governs.
Unreviewed NEC 220 values (5) Transcribed from secondary sources and not yet checked against NFPA 70
(2020). They compute.
220.14(I), single or multiple receptacle on one yoke uses 180 VA per yoke Table 220.44, first band limit uses 10000 VA Table 220.44, first band factor uses 1 (demand factor) Table 220.44, remainder factor uses 0.5 (demand factor) 220.14(K), office receptacle minimum uses 1 VA/ft² LP-O2 Panel Unreviewed data
17,076 23,140 (uses unreviewed table data) 80.83 80.83 80.83 (line C) 208 V 3-ph Calculated The figures below use 5 NEC 220
values not yet checked against the
code book, listed at the end.
Category breakdown Category Connected VA Demand VA Continuous at 125 % Rule ReceptaclesTable 220.44: first 10 kVA at 100 %, the rest at 50 %, with the 220.14(K) office minimum 3,060 8,500 8,500 Table 220.44: first 10 kVA at 100 %, the rest at 50 %, with the 220.14(K) office minimum Motor220.50 and 430.24: every motor plus 25 % of the largest 2,496 3,120 3,120 220.50 and 430.24: every motor plus 25 % of the largest Other (nameplate)220.14(A): nameplate at 100 % 11,520 11,520 13,545 220.14(A): nameplate at 100 %
Noncoincident loads (220.60) No noncoincident groups below this node.
Currents At 208 V, 3-phase, 3 poles, from the supply that feeds it.
Maximum load 80.83 A Balanced 64.23 A; heaviest line 80.83 (line C). The heaviest line governs.
Continuous at 125 % 80.83 A Balanced 69.85 A; heaviest line 80.83 (line C). The heaviest line governs.
Unreviewed NEC 220 values (5) Transcribed from secondary sources and not yet checked against NFPA 70
(2020). They compute.
220.14(I), single or multiple receptacle on one yoke uses 180 VA per yoke Table 220.44, first band limit uses 10000 VA Table 220.44, first band factor uses 1 (demand factor) Table 220.44, remainder factor uses 0.5 (demand factor) 220.14(K), office receptacle minimum uses 1 VA/ft² Open LP-O2 in the panel editor