DEMO - Harborline Office
Fictional 8,500 sf office fit-out with open work areas, meeting rooms, a breakroom and a small IT room. Demonstration data only; no real client, person or address is represented.
- Calculated
- 2026-11-22
- Fingerprint
- fnv1a32:d055d541
- %Z tolerance
- × 0.9
- Line to neutral, 1Ø
- × 1.5
- Motor contribution
- 4 × motor FLA
2 runs use a C value from Eaton Table 4 that is not yet checked against the book. Values that depend on it are calculated and marked unreviewed.
| Equipment and system | Available | Motor contribution | AIC 110.9 | SCCR 408.6 |
|---|---|---|---|---|
| Utility source · 120/208Y V 3Ø | 21.4 kA | 833 A | Not checked | Not checked |
| ||||
| Meter · 120/208Y V 3Ø | 21.4 kA | 833 A | Not checked | Not checked |
| ||||
| Disconnect · 120/208Y V 3Ø Service · 110.24 | 21.4 kA | 833 A | Not checked | Not checked |
| ||||
| Panel · 120/208Y V 3Ø | 16.9 kA Unreviewed C value | 833 A | 22 kA Passunder 110.9 | 22 kA Passunder 408.6 |
Issues
| ||||
| Disconnect · 120/208Y V 3Ø Service · 110.24 | 21.4 kA | 833 A | Not checked | Not checked |
| ||||
| Panel · 120/208Y V 3Ø | 6.2 kA Unreviewed C value | 833 A | 10 kA Passunder 110.9 | 10 kA Passunder 408.6 |
Issues
| ||||