LP-O1 (EAST ELECTRICAL CLOSET)
LP-O1
MAIN:M.C.B.RATING:225 ASPACES:42SERVICE: 120/208 V, 3-PHASE, 4-WIREMOUNTING: FLUSHFEEDS FROM: BUILDING DISTRIBUTION / 225 A FEEDERPANEL SCCR: 22 KATRIM: HINGED DOOR, NEMA 1A.I.C.: 22 KAFAULT CURRENT CALCULATED 2026-11-22 / fnv1a32:d055d541AFC: 16.9 KA, uses Eaton Table 4 C values not yet checked against the bookA.I.C. PASS, SCCR PASS| CKT | DESCRIPTION | KVA | CIRCUIT BREAKER | BRANCH CIRCUIT | C | VD% | PH | CKT | DESCRIPTION | KVA | CIRCUIT BREAKER | BRANCH CIRCUIT | C | VD% | PH | ||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| POLE | TRIP | P | N | GND | POLE | TRIP | P | N | GND | ||||||||||||
| 1 | 1.2 | 1 | 20 | 10 | 10 | 10 | -- | 2.88 | A | 2 | 1.2 | 1 | 20 | 8 | 8 | 8 | -- | 2.30 | A | ||
| 3 | 1.8 | 1 | 20 | 10 | 10 | 10 | -- | 2.24 | B | 4 | 1.8 | 1 | 20 | 10 | 10 | 10 | -- | 2.56 | B | ||
| 5 | 1.8 | 1 | 20 | 8 | 8 | 8 | -- | 1.98 | C | 6 | 1.8 | 1 | 20 | 8 | 8 | 8 | -- | 2.19 | C | ||
| 7 | 1.44 | 1 | 20 | 10 | 10 | 10 | -- | 1.92 | A | 8 | 1.44 | 1 | 20 | 10 | 10 | 10 | -- | 2.40 | A | ||
| 9 | 1.8 | 1 | 20 | 12 | 12 | 12 | -- | 2.94 | B | 10 | 1.08 | 1 | 20 | 10 | 10 | 10 | -- | 2.08 | B | ||
| 11 | 1.2 | 1 | 20 | 10 | 10 | 10 | -- | 2.24 | C | 12 | 1.2 | 1 | 20 | 10 | 10 | 10 | -- | 2.72 | C | ||
| 13 | -- | -- | -- | -- | -- | -- | -- | -- | A | 14 | -- | -- | -- | -- | -- | -- | -- | -- | A | ||
| 15 | -- | 1 | 20 | -- | -- | -- | -- | -- | B | 16 | -- | 1 | 20 | -- | -- | -- | -- | -- | B | ||
| 17 | -- | -- | -- | -- | -- | -- | -- | -- | C | 18 | -- | -- | -- | -- | -- | -- | -- | -- | C | ||
| 19 | -- | -- | -- | -- | -- | -- | -- | -- | A | 20 | -- | -- | -- | -- | -- | -- | -- | -- | A | ||
| 21 | -- | -- | -- | -- | -- | -- | -- | -- | B | 22 | -- | -- | -- | -- | -- | -- | -- | -- | B | ||
| 23 | -- | -- | -- | -- | -- | -- | -- | -- | C | 24 | -- | -- | -- | -- | -- | -- | -- | -- | C | ||
| 25 | -- | -- | -- | -- | -- | -- | -- | -- | A | 26 | -- | -- | -- | -- | -- | -- | -- | -- | A | ||
| 27 | -- | -- | -- | -- | -- | -- | -- | -- | B | 28 | -- | -- | -- | -- | -- | -- | -- | -- | B | ||
| 29 | -- | -- | -- | -- | -- | -- | -- | -- | C | 30 | -- | -- | -- | -- | -- | -- | -- | -- | C | ||
| 31 | -- | -- | -- | -- | -- | -- | -- | -- | A | 32 | -- | -- | -- | -- | -- | -- | -- | -- | A | ||
| 33 | -- | -- | -- | -- | -- | -- | -- | -- | B | 34 | -- | -- | -- | -- | -- | -- | -- | -- | B | ||
| 35 | -- | -- | -- | -- | -- | -- | -- | -- | C | 36 | -- | -- | -- | -- | -- | -- | -- | -- | C | ||
| 37 | -- | -- | -- | -- | -- | -- | -- | -- | A | 38 | -- | -- | -- | -- | -- | -- | -- | -- | A | ||
| 39 | -- | -- | -- | -- | -- | -- | -- | -- | B | 40 | -- | -- | -- | -- | -- | -- | -- | -- | B | ||
| 41 | -- | -- | -- | -- | -- | -- | -- | -- | C | 42 | -- | -- | -- | -- | -- | -- | -- | -- | C | ||
CONNECTED LOAD: 17.76 KVAPHASE A: 44.0 APHASE B: 54.0 APHASE C: 50.0 AIMBALANCE: 20.3% | |||||||||||||||||||||
WORST COMBINED VOLTAGE DROP: 3.31% AT CKT 9, C405.5.3, uses Table 9 values not yet checked against the book | |||||||||||||||||||||
CALCULATED LOAD: 23.43 KVA (23.43 KVA CONTINUOUS AT 125%)MAXIMUM LOAD: 74.48 A, 33% OF 225 A MAIN, HEAVIEST LINE CCONTINUOUS AT 125%: 74.48 A, 33% OF 225 A MAIN, HEAVIEST LINE C | |||||||||||||||||||||
GENERAL LIGHTINGCOUNTED 4.80 KVADEMAND 11.05 KVATable 220.12 unit load or 125 % of connected, whichever is larger, then Table 220.42 | |||||||||||||||||||||
RECEPTACLESCOUNTED 11.16 KVADEMAND 10.58 KVATable 220.44: first 10 kVA at 100 %, the rest at 50 %, with the 220.14(K) office minimum | |||||||||||||||||||||
OTHER (NAMEPLATE)COUNTED 1.80 KVADEMAND 1.80 KVA220.14(A): nameplate at 100 % | |||||||||||||||||||||
| Unreviewed data: the calculated load uses NEC 2020 values not yet checked against the book: Table 220.12 (Office); Table 220.42 (All others, total factor); 220.14(I) (single or multiple receptacle on one yoke); Table 220.44 (first band limit, first band factor, remainder factor); 220.14(K) (office receptacle minimum). | |||||||||||||||||||||
| NOTES: Synthetic demonstration schedule. Connected loads, run lengths, raceways, installed conductor sizes, load categories, served areas, equipment ratings, energy code scope and fault-current inputs are fictional. Table values are not yet checked against the book. | |||||||||||||||||||||
| Unreviewed data: 1 C value from Eaton's Short-Circuit Current Calculations (2014), Table 4, three single conductors at 600 V, used on the run to LP-O1, not yet checked against the bulletin: copper in steel conduit: 4/0 AWG. get_fault_current lists each value and where it is used. | |||||||||||||||||||||
Calculated load
Calculated23.43 kVA23.43 kVA with continuous loads at 125 %
- Maximum load
- 74.48 A 33 % of the 225 A mainheaviest line C
- Continuous at 125 %
- 74.48 A 33 % of the 225 A mainheaviest line C
At 208 V, three-phase.
| Category | Counted | Demand | Rule |
|---|---|---|---|
| General lighting | 4.80 kVA | 11.05 kVA | Table 220.12 unit load or 125 % of connected, whichever is larger, then Table 220.42 |
| Receptacles | 11.16 kVA | 10.58 kVA | Table 220.44: first 10 kVA at 100 %, the rest at 50 %, with the 220.14(K) office minimum |
| Other (nameplate) | 1.80 kVA | 1.80 kVA | 220.14(A): nameplate at 100 % |
- Unreviewed data: 7 table values (Table 220.12, Table 220.42, 220.14(I), Table 220.44, 220.14(K)) not yet checked against the code book.