DEMO - Juniper Dental Studio
Fictional 3,200 sf tenant improvement with four operatories, sterilization, imaging and dedicated dental air and vacuum equipment. Demonstration data only; no real client, person or address is represented.
FBC, Energy Conservation, 8th Edition (2023), C405.5.3: feeders and branch circuits combined sized for at most 5 percent voltage drop.
- Pass
- 20
- Fail
- 0
- REQ
- 0
- Not calculated
- 0
26 Table 9 values used here are not yet checked against the book. They still compute; rows that use one are marked.
- NFPA-70-2020/Chapter 9/Table 9/AC Resistance Uncoated Copper Steel Conduit/4/0 AWG Unreviewed data: NEC 2020 Chapter 9, Table 9, AC Resistance Uncoated Copper Steel Conduit, 4/0 AWG (0.063 ohms per 1000 ft) has not been checked against the book.
- NFPA-70-2020/Chapter 9/Table 9/XL Steel Conduit/4/0 AWG Unreviewed data: NEC 2020 Chapter 9, Table 9, XL Steel Conduit, 4/0 AWG (0.051 ohms per 1000 ft) has not been checked against the book.
- NFPA-70-2020/Chapter 9/Table 9/AC Resistance Uncoated Copper Steel Conduit/1 AWG Unreviewed data: NEC 2020 Chapter 9, Table 9, AC Resistance Uncoated Copper Steel Conduit, 1 AWG (0.16 ohms per 1000 ft) has not been checked against the book.
- NFPA-70-2020/Chapter 9/Table 9/XL Steel Conduit/1 AWG Unreviewed data: NEC 2020 Chapter 9, Table 9, XL Steel Conduit, 1 AWG (0.057 ohms per 1000 ft) has not been checked against the book.
- NFPA-70-2020/Chapter 9/Table 9/AC Resistance Uncoated Copper Steel Conduit/10 AWG Unreviewed data: NEC 2020 Chapter 9, Table 9, AC Resistance Uncoated Copper Steel Conduit, 10 AWG (1.2 ohms per 1000 ft) has not been checked against the book.
- NFPA-70-2020/Chapter 9/Table 9/XL Steel Conduit/10 AWG Unreviewed data: NEC 2020 Chapter 9, Table 9, XL Steel Conduit, 10 AWG (0.063 ohms per 1000 ft) has not been checked against the book.
- NFPA-70-2020/Chapter 9/Table 9/AC Resistance Uncoated Copper Steel Conduit/12 AWG Unreviewed data: NEC 2020 Chapter 9, Table 9, AC Resistance Uncoated Copper Steel Conduit, 12 AWG (2.0 ohms per 1000 ft) has not been checked against the book.
- NFPA-70-2020/Chapter 9/Table 9/XL Steel Conduit/12 AWG Unreviewed data: NEC 2020 Chapter 9, Table 9, XL Steel Conduit, 12 AWG (0.068 ohms per 1000 ft) has not been checked against the book.
- NFPA-70-2020/Chapter 9/Table 9/AC Resistance Uncoated Copper Steel Conduit/8 AWG Unreviewed data: NEC 2020 Chapter 9, Table 9, AC Resistance Uncoated Copper Steel Conduit, 8 AWG (0.78 ohms per 1000 ft) has not been checked against the book.
- NFPA-70-2020/Chapter 9/Table 9/XL Steel Conduit/8 AWG Unreviewed data: NEC 2020 Chapter 9, Table 9, XL Steel Conduit, 8 AWG (0.065 ohms per 1000 ft) has not been checked against the book.
- NFPA-70-2020/Chapter 9/Table 9/AC Resistance Uncoated Copper Steel Conduit/6 AWG Unreviewed data: NEC 2020 Chapter 9, Table 9, AC Resistance Uncoated Copper Steel Conduit, 6 AWG (0.49 ohms per 1000 ft) has not been checked against the book.
- NFPA-70-2020/Chapter 9/Table 9/XL Steel Conduit/6 AWG Unreviewed data: NEC 2020 Chapter 9, Table 9, XL Steel Conduit, 6 AWG (0.064 ohms per 1000 ft) has not been checked against the book.
- NFPA-70-2020/Chapter 9/Table 9/AC Resistance Uncoated Copper Steel Conduit/4 AWG Unreviewed data: NEC 2020 Chapter 9, Table 9, AC Resistance Uncoated Copper Steel Conduit, 4 AWG (0.31 ohms per 1000 ft) has not been checked against the book.
- NFPA-70-2020/Chapter 9/Table 9/XL Steel Conduit/4 AWG Unreviewed data: NEC 2020 Chapter 9, Table 9, XL Steel Conduit, 4 AWG (0.060 ohms per 1000 ft) has not been checked against the book.
- NFPA-70-2020/Chapter 9/Table 9/AC Resistance Uncoated Copper Steel Conduit/3 AWG Unreviewed data: NEC 2020 Chapter 9, Table 9, AC Resistance Uncoated Copper Steel Conduit, 3 AWG (0.25 ohms per 1000 ft) has not been checked against the book.
- NFPA-70-2020/Chapter 9/Table 9/XL Steel Conduit/3 AWG Unreviewed data: NEC 2020 Chapter 9, Table 9, XL Steel Conduit, 3 AWG (0.059 ohms per 1000 ft) has not been checked against the book.
- NFPA-70-2020/Chapter 9/Table 9/AC Resistance Uncoated Copper Steel Conduit/2 AWG Unreviewed data: NEC 2020 Chapter 9, Table 9, AC Resistance Uncoated Copper Steel Conduit, 2 AWG (0.20 ohms per 1000 ft) has not been checked against the book.
- NFPA-70-2020/Chapter 9/Table 9/XL Steel Conduit/2 AWG Unreviewed data: NEC 2020 Chapter 9, Table 9, XL Steel Conduit, 2 AWG (0.057 ohms per 1000 ft) has not been checked against the book.
- NFPA-70-2020/Chapter 9/Table 9/AC Resistance Uncoated Copper Steel Conduit/1/0 AWG Unreviewed data: NEC 2020 Chapter 9, Table 9, AC Resistance Uncoated Copper Steel Conduit, 1/0 AWG (0.12 ohms per 1000 ft) has not been checked against the book.
- NFPA-70-2020/Chapter 9/Table 9/XL Steel Conduit/1/0 AWG Unreviewed data: NEC 2020 Chapter 9, Table 9, XL Steel Conduit, 1/0 AWG (0.055 ohms per 1000 ft) has not been checked against the book.
- NFPA-70-2020/Chapter 9/Table 9/AC Resistance Uncoated Copper Steel Conduit/2/0 AWG Unreviewed data: NEC 2020 Chapter 9, Table 9, AC Resistance Uncoated Copper Steel Conduit, 2/0 AWG (0.10 ohms per 1000 ft) has not been checked against the book.
- NFPA-70-2020/Chapter 9/Table 9/XL Steel Conduit/2/0 AWG Unreviewed data: NEC 2020 Chapter 9, Table 9, XL Steel Conduit, 2/0 AWG (0.054 ohms per 1000 ft) has not been checked against the book.
- NFPA-70-2020/Chapter 9/Table 9/AC Resistance Uncoated Copper Steel Conduit/3/0 AWG Unreviewed data: NEC 2020 Chapter 9, Table 9, AC Resistance Uncoated Copper Steel Conduit, 3/0 AWG (0.079 ohms per 1000 ft) has not been checked against the book.
- NFPA-70-2020/Chapter 9/Table 9/XL Steel Conduit/3/0 AWG Unreviewed data: NEC 2020 Chapter 9, Table 9, XL Steel Conduit, 3/0 AWG (0.052 ohms per 1000 ft) has not been checked against the book.
- NFPA-70-2020/Chapter 9/Table 9/AC Resistance Uncoated Copper Steel Conduit/14 AWG Unreviewed data: NEC 2020 Chapter 9, Table 9, AC Resistance Uncoated Copper Steel Conduit, 14 AWG (3.1 ohms per 1000 ft) has not been checked against the book.
- NFPA-70-2020/Chapter 9/Table 9/XL Steel Conduit/14 AWG Unreviewed data: NEC 2020 Chapter 9, Table 9, XL Steel Conduit, 14 AWG (0.073 ohms per 1000 ft) has not been checked against the book.
Scroll each table sideways for the drop, allowance and state columns.
| Equipment | Fed from | Length (ft) | Size | Drop | Allowance | Cumulative |
|---|---|---|---|---|---|---|
| SD-1Disconnect | U-2 | -- | Bus | 0.00 % | -- | Not countedabove the start point |
| LP-D1Panel | SD-1 | 70 | 4/0 AWG | 1.06 %Uses 2 unreviewed Table 9 values2.21 V | 2.00 % | 1.06 %Uses 2 unreviewed Table 9 valuesfrom SD-1 |
| SD-2Disconnect | U-2 | -- | Bus | 0.00 % | -- | Not countedabove the start point |
| MP-D1Panel | SD-2 | 55 | 1 AWG | 0.97 %Uses 2 unreviewed Table 9 values2.02 V | 2.00 % | 0.97 %Uses 2 unreviewed Table 9 valuesfrom SD-2 |
LP-D1
| Ckt | Description | Length (ft) | Current | Size | Drop | Allowance | Min size | Combined | State |
|---|---|---|---|---|---|---|---|---|---|
| 1 | Reception and waiting lighting | 60 | 16.00 A80 % of trip | 10 AWG | 1.92 %Uses 2 unreviewed Table 9 values2.31 V | 3.00 % | 10 AWGUses 24 unreviewed Table 9 values | 2.99 %Uses 4 unreviewed Table 9 values | Pass |
| 2 | Operatory lighting | 75 | 16.00 A80 % of trip | 10 AWG | 2.40 %Uses 2 unreviewed Table 9 values2.88 V | 3.00 % | 10 AWGUses 24 unreviewed Table 9 values | 3.47 %Uses 4 unreviewed Table 9 values | Pass |
| 3 | Operatory 1 receptacles | 55 | 16.00 A80 % of trip | 12 AWG | 2.94 %Uses 2 unreviewed Table 9 values3.52 V | 3.00 % | 12 AWGUses 26 unreviewed Table 9 values | 4.00 %Uses 4 unreviewed Table 9 values | Pass |
| 4 | Operatory 2 receptacles | 65 | 16.00 A80 % of trip | 10 AWG | 2.08 %Uses 2 unreviewed Table 9 values2.50 V | 3.00 % | 10 AWGUses 24 unreviewed Table 9 values | 3.15 %Uses 4 unreviewed Table 9 values | Pass |
| 5 | Operatory 3 receptacles | 75 | 16.00 A80 % of trip | 10 AWG | 2.40 %Uses 2 unreviewed Table 9 values2.88 V | 3.00 % | 10 AWGUses 24 unreviewed Table 9 values | 3.47 %Uses 4 unreviewed Table 9 values | Pass |
| 6 | Operatory 4 receptacles | 85 | 16.00 A80 % of trip | 10 AWG | 2.72 %Uses 2 unreviewed Table 9 values3.27 V | 3.00 % | 10 AWGUses 24 unreviewed Table 9 values | 3.79 %Uses 4 unreviewed Table 9 values | Pass |
| 7 | Reception workstations | 45 | 16.00 A80 % of trip | 12 AWG | 2.40 %Uses 2 unreviewed Table 9 values2.88 V | 3.00 % | 12 AWGUses 26 unreviewed Table 9 values | 3.46 %Uses 4 unreviewed Table 9 values | Pass |
| 8 | IT cabinet and network | 30 | 16.00 A80 % of trip | 12 AWG | 1.60 %Uses 2 unreviewed Table 9 values1.92 V | 3.00 % | 14 AWGUses 26 unreviewed Table 9 values | 2.66 %Uses 4 unreviewed Table 9 values | Pass |
| 9 | Staff breakroom receptacles | 50 | 16.00 A80 % of trip | 12 AWG | 2.67 %Uses 2 unreviewed Table 9 values3.20 V | 3.00 % | 12 AWGUses 26 unreviewed Table 9 values | 3.73 %Uses 4 unreviewed Table 9 values | Pass |
| 10 | Sterilization countertop | 40 | 16.00 A80 % of trip | 12 AWG | 2.13 %Uses 2 unreviewed Table 9 values2.56 V | 3.00 % | 12 AWGUses 26 unreviewed Table 9 values | 3.20 %Uses 4 unreviewed Table 9 values | Pass |
| 11 | Support room lighting | 35 | 16.00 A80 % of trip | 12 AWG | 1.87 %Uses 2 unreviewed Table 9 values2.24 V | 3.00 % | 14 AWGUses 26 unreviewed Table 9 values | 2.93 %Uses 4 unreviewed Table 9 values | Pass |
| 12 | Restroom receptacles | 45 | 16.00 A80 % of trip | 12 AWG | 2.40 %Uses 2 unreviewed Table 9 values2.88 V | 3.00 % | 12 AWGUses 26 unreviewed Table 9 values | 3.46 %Uses 4 unreviewed Table 9 values | Pass |
MP-D1
| Ckt | Description | Length (ft) | Current | Size | Drop | Allowance | Min size | Combined | State |
|---|---|---|---|---|---|---|---|---|---|
| 1,3,5 | Dental air compressor | 25 | 24.00 A80 % of trip | 10 AWG | 0.60 %Uses 2 unreviewed Table 9 values1.25 V | 3.00 % | 14 AWGUses 26 unreviewed Table 9 values | 1.57 %Uses 4 unreviewed Table 9 values | Pass |
| 2,4,6 | Dental vacuum system | 30 | 24.00 A80 % of trip | 10 AWG | 0.72 %Uses 2 unreviewed Table 9 values1.50 V | 3.00 % | 14 AWGUses 26 unreviewed Table 9 values | 1.69 %Uses 4 unreviewed Table 9 values | Pass |
| 7,9 | Sterilizer 1 | 60 | 24.00 A80 % of trip | 10 AWG | 1.66 %Uses 2 unreviewed Table 9 values3.46 V | 3.00 % | 12 AWGUses 26 unreviewed Table 9 values | 2.64 %Uses 4 unreviewed Table 9 values | Pass |
| 8,10 | Sterilizer 2 | 65 | 24.00 A80 % of trip | 10 AWG | 1.80 %Uses 2 unreviewed Table 9 values3.75 V | 3.00 % | 10 AWGUses 24 unreviewed Table 9 values | 2.77 %Uses 4 unreviewed Table 9 values | Pass |
| 11,13 | Imaging equipment | 70 | 16.00 A80 % of trip | 12 AWG | 2.16 %Uses 2 unreviewed Table 9 values4.48 V | 3.00 % | 12 AWGUses 26 unreviewed Table 9 values | 3.13 %Uses 4 unreviewed Table 9 values | Pass |
| 12,14,16 | Packaged HVAC unit | 45 | 32.00 A80 % of trip | 8 AWG | 0.94 %Uses 2 unreviewed Table 9 values1.95 V | 3.00 % | 12 AWGUses 26 unreviewed Table 9 values | 1.91 %Uses 4 unreviewed Table 9 values | Pass |
| 17,19 | Water heater | 35 | 21.63 Aconnected load | 10 AWG | 0.87 %Uses 2 unreviewed Table 9 values1.82 V | 3.00 % | 14 AWGUses 26 unreviewed Table 9 values | 1.85 %Uses 4 unreviewed Table 9 values | Pass |
| 18 | Equipment room receptacle | 15 | 16.00 A80 % of trip | 12 AWG | 0.80 %Uses 2 unreviewed Table 9 values0.96 V | 3.00 % | 14 AWGUses 26 unreviewed Table 9 values | 1.77 %Uses 4 unreviewed Table 9 values | Pass |