LP-D1 (ELECTRICAL CLOSET)
LP-D1
MAIN:M.C.B.RATING:225 ASPACES:42SERVICE: 120/208 V, 3-PHASE, 4-WIREMOUNTING: FLUSHFEEDS FROM: BUILDING DISTRIBUTION / 225 A FEEDERPANEL SCCR: 22 KATRIM: HINGED DOOR, NEMA 1A.I.C.: 22 KAFAULT CURRENT CALCULATED 2026-11-22 / fnv1a32:12fde621AFC: 12.2 KA, uses Eaton Table 4 C values not yet checked against the bookA.I.C. PASS, SCCR PASS
Panel schedule for LP-D1, odd circuits on the left and even circuits on the right
CKTDESCRIPTIONKVACIRCUIT BREAKERBRANCH CIRCUITCVD%PHCKTDESCRIPTIONKVACIRCUIT BREAKERBRANCH CIRCUITCVD%PH
POLETRIPPNGNDPOLETRIPPNGND
10.96120101010--1.92A21.2120101010--2.40A
31.8120121212--2.94B41.8120101010--2.08B
51.8120101010--2.40C61.8120101010--2.72C
71.44120121212--2.40A81.2120121212--1.60A
91.5120121212--2.67B101.8120121212--2.13B
110.9120121212--1.87C121.2120121212--2.40C
13----------------A14----------------A
15--120----------B16--120----------B
17----------------C18----------------C
19----------------A20----------------A
21----------------B22----------------B
23----------------C24----------------C
25----------------A26----------------A
27----------------B28----------------B
29----------------C30----------------C
31----------------A32----------------A
33----------------B34----------------B
35----------------C36----------------C
37----------------A38----------------A
39----------------B40----------------B
41----------------C42----------------C
CONNECTED LOAD: 17.4 KVAPHASE A: 40.0 APHASE B: 57.5 APHASE C: 47.5 AIMBALANCE: 36.2%
WORST COMBINED VOLTAGE DROP: 4.00% AT CKT 3, C405.5.3, uses Table 9 values not yet checked against the book
CALCULATED LOAD: 17.80 KVA (18.10 KVA CONTINUOUS AT 125%)MAXIMUM LOAD: 50.75 A, 23% OF 225 A MAIN, HEAVIEST LINE ACONTINUOUS AT 125%: 53.25 A, 24% OF 225 A MAIN, HEAVIEST LINE A
GENERAL LIGHTINGCOUNTED 3.06 KVADEMAND 5.12 KVATable 220.12 unit load or 125 % of connected, whichever is larger, then Table 220.42
RECEPTACLESCOUNTED 12.96 KVADEMAND 11.48 KVATable 220.44: first 10 kVA at 100 %, the rest at 50 %
OTHER (NAMEPLATE)COUNTED 1.20 KVADEMAND 1.20 KVA220.14(A): nameplate at 100 %
Unreviewed data: the calculated load uses NEC 2020 values not yet checked against the book: Table 220.12 (Health care clinic); Table 220.42 (All others, total factor); 220.14(I) (single or multiple receptacle on one yoke); Table 220.44 (first band limit, first band factor, remainder factor).
NOTES: Synthetic demonstration schedule. Connected loads, run lengths, raceways, installed conductor sizes, load categories, served areas, equipment ratings, energy code scope and fault-current inputs are fictional. Table values are not yet checked against the book.
Unreviewed data: 1 C value from Eaton's Short-Circuit Current Calculations (2014), Table 4, three single conductors at 600 V, used on the run to LP-D1, not yet checked against the bulletin: copper in steel conduit: 4/0 AWG. get_fault_current lists each value and where it is used.

Calculated load

Calculated

17.80 kVA18.10 kVA with continuous loads at 125 %

Maximum load
50.75 A 23 % of the 225 A mainheaviest line A
Continuous at 125 %
53.25 A 24 % of the 225 A mainheaviest line A

At 208 V, three-phase.

Calculated load by category
CategoryCountedDemandRule
General lighting3.06 kVA5.12 kVATable 220.12 unit load or 125 % of connected, whichever is larger, then Table 220.42
Receptacles12.96 kVA11.48 kVATable 220.44: first 10 kVA at 100 %, the rest at 50 %
Other (nameplate)1.20 kVA1.20 kVA220.14(A): nameplate at 100 %
  • Unreviewed data: 6 table values (Table 220.12, Table 220.42, 220.14(I), Table 220.44) not yet checked against the code book.