DEMO - Juniper Dental Studio
Fictional 3,200 sf tenant improvement with four operatories, sterilization, imaging and dedicated dental air and vacuum equipment. Demonstration data only; no real client, person or address is represented.
- Calculated
- 2026-11-22
- Fingerprint
- fnv1a32:12fde621
- %Z tolerance
- × 0.9
- Line to neutral, 1Ø
- × 1.5
- Motor contribution
- 4 × motor FLA
2 runs use a C value from Eaton Table 4 that is not yet checked against the book. Values that depend on it are calculated and marked unreviewed.
| Equipment and system | Available | Motor contribution | AIC 110.9 | SCCR 408.6 |
|---|---|---|---|---|
| Utility source · 120/208Y V 3Ø | 22.3 kA | 210 A | Not checked | Not checked |
| ||||
| Disconnect · 120/208Y V 3Ø Service · 110.24 | 22.3 kA | 210 A | Not checked | Not checked |
| ||||
| Panel · 120/208Y V 3Ø | 12.2 kA Unreviewed C value | 210 A | 22 kA Passunder 110.9 | 22 kA Passunder 408.6 |
Issues
| ||||
| Disconnect · 120/208Y V 3Ø Service · 110.24 | 22.3 kA | 210 A | Not checked | Not checked |
| ||||
| Panel · 120/208Y V 3Ø | 9.5 kA Unreviewed C value | 210 A | 22 kA Passunder 110.9 | 22 kA Passunder 408.6 |
Issues
| ||||