Fault current

Download table SVG
Calculated
2026-11-22
Fingerprint
fnv1a32:12fde621
%Z tolerance
× 0.9
Line to neutral, 1Ø
× 1.5
Motor contribution
4 × motor FLA

2 runs use a C value from Eaton Table 4 that is not yet checked against the book. Values that depend on it are calculated and marked unreviewed.

Equipment and systemAvailableMotor contributionAIC 110.9SCCR 408.6
Utility source · 120/208Y V 3Ø 22.3 kA 210 ANot checkedNot checked
Disconnect · 120/208Y V 3Ø Service · 110.24 22.3 kA 210 ANot checkedNot checked
Panel · 120/208Y V 3Ø 12.2 kA Unreviewed C value 210 A22 kA Passunder 110.922 kA Passunder 408.6
Disconnect · 120/208Y V 3Ø Service · 110.24 22.3 kA 210 ANot checkedNot checked
Panel · 120/208Y V 3Ø 9.5 kA Unreviewed C value 210 A22 kA Passunder 110.922 kA Passunder 408.6