SD-1 Disconnect Unreviewed data
17,220 17,800 (uses unreviewed table data) 50.75 53.25 50.75 (line A) 208 V 3-ph Calculated The figures below use 6 NEC 220
values not yet checked against the
code book, listed at the end.
Category breakdown Category Connected VA Demand VA Continuous at 125 % Rule General lightingTable 220.12 unit load or 125 % of connected, whichever is larger, then Table 220.42 3,060 5,120 5,120 Table 220.12 unit load or 125 % of connected, whichever is larger, then Table 220.42 ReceptaclesTable 220.44: first 10 kVA at 100 %, the rest at 50 % 12,960 11,480 11,480 Table 220.44: first 10 kVA at 100 %, the rest at 50 % Other (nameplate)220.14(A): nameplate at 100 % 1,200 1,200 1,500 220.14(A): nameplate at 100 %
Noncoincident loads (220.60) No noncoincident groups below this node.
Currents At 208 V, 3-phase, 3 poles, from the supply that feeds it.
Maximum load 50.75 A Balanced 49.41 A; heaviest line 50.75 (line A). The heaviest line governs.
Continuous at 125 % 53.25 A Balanced 50.24 A; heaviest line 53.25 (line A). The heaviest line governs.
Unreviewed NEC 220 values (6) Transcribed from secondary sources and not yet checked against NFPA 70
(2020). They compute.
Table 220.12, Health care clinic uses 1.6 VA/ft² Table 220.42, All others, total factor uses 1 (demand factor) 220.14(I), single or multiple receptacle on one yoke uses 180 VA per yoke Table 220.44, first band limit uses 10000 VA Table 220.44, first band factor uses 1 (demand factor) Table 220.44, remainder factor uses 0.5 (demand factor) LP-D1 Panel Unreviewed data
17,220 17,800 (uses unreviewed table data) 50.75 53.25 50.75 (line A) 208 V 3-ph Calculated The figures below use 6 NEC 220
values not yet checked against the
code book, listed at the end.
Category breakdown Category Connected VA Demand VA Continuous at 125 % Rule General lightingTable 220.12 unit load or 125 % of connected, whichever is larger, then Table 220.42 3,060 5,120 5,120 Table 220.12 unit load or 125 % of connected, whichever is larger, then Table 220.42 ReceptaclesTable 220.44: first 10 kVA at 100 %, the rest at 50 % 12,960 11,480 11,480 Table 220.44: first 10 kVA at 100 %, the rest at 50 % Other (nameplate)220.14(A): nameplate at 100 % 1,200 1,200 1,500 220.14(A): nameplate at 100 %
Noncoincident loads (220.60) No noncoincident groups below this node.
Currents At 208 V, 3-phase, 3 poles, from the supply that feeds it.
Maximum load 50.75 A Balanced 49.41 A; heaviest line 50.75 (line A). The heaviest line governs.
Continuous at 125 % 53.25 A Balanced 50.24 A; heaviest line 53.25 (line A). The heaviest line governs.
Unreviewed NEC 220 values (6) Transcribed from secondary sources and not yet checked against NFPA 70
(2020). They compute.
Table 220.12, Health care clinic uses 1.6 VA/ft² Table 220.42, All others, total factor uses 1 (demand factor) 220.14(I), single or multiple receptacle on one yoke uses 180 VA per yoke Table 220.44, first band limit uses 10000 VA Table 220.44, first band factor uses 1 (demand factor) Table 220.44, remainder factor uses 0.5 (demand factor) Open LP-D1 in the panel editor
SD-2 Disconnect Unreviewed data
34,094 36,346 (uses unreviewed table data) 117.46 122.16 117.46 (line A) 208 V 3-ph Calculated The figures below use 4 NEC 220
values not yet checked against the
code book, listed at the end.
Category breakdown Category Connected VA Demand VA Continuous at 125 % Rule ReceptaclesTable 220.44: first 10 kVA at 100 %, the rest at 50 % 1,080 1,080 1,080 Table 220.44: first 10 kVA at 100 %, the rest at 50 % Motor220.50 and 430.24: every motor plus 25 % of the largest 18,914 21,166 21,166 220.50 and 430.24: every motor plus 25 % of the largest Other (nameplate)220.14(A): nameplate at 100 % 14,100 14,100 15,225 220.14(A): nameplate at 100 %
Noncoincident loads (220.60) No noncoincident groups below this node.
Currents At 208 V, 3-phase, 3 poles, from the supply that feeds it.
Maximum load 117.46 A Balanced 100.89 A; heaviest line 117.46 (line A). The heaviest line governs.
Continuous at 125 % 122.16 A Balanced 104.01 A; heaviest line 122.16 (line A). The heaviest line governs.
Unreviewed NEC 220 values (4) Transcribed from secondary sources and not yet checked against NFPA 70
(2020). They compute.
220.14(I), single or multiple receptacle on one yoke uses 180 VA per yoke Table 220.44, first band limit uses 10000 VA Table 220.44, first band factor uses 1 (demand factor) Table 220.44, remainder factor uses 0.5 (demand factor) MP-D1 Panel Unreviewed data
34,094 36,346 (uses unreviewed table data) 117.46 122.16 117.46 (line A) 208 V 3-ph Calculated The figures below use 4 NEC 220
values not yet checked against the
code book, listed at the end.
Category breakdown Category Connected VA Demand VA Continuous at 125 % Rule ReceptaclesTable 220.44: first 10 kVA at 100 %, the rest at 50 % 1,080 1,080 1,080 Table 220.44: first 10 kVA at 100 %, the rest at 50 % Motor220.50 and 430.24: every motor plus 25 % of the largest 18,914 21,166 21,166 220.50 and 430.24: every motor plus 25 % of the largest Other (nameplate)220.14(A): nameplate at 100 % 14,100 14,100 15,225 220.14(A): nameplate at 100 %
Noncoincident loads (220.60) No noncoincident groups below this node.
Currents At 208 V, 3-phase, 3 poles, from the supply that feeds it.
Maximum load 117.46 A Balanced 100.89 A; heaviest line 117.46 (line A). The heaviest line governs.
Continuous at 125 % 122.16 A Balanced 104.01 A; heaviest line 122.16 (line A). The heaviest line governs.
Unreviewed NEC 220 values (4) Transcribed from secondary sources and not yet checked against NFPA 70
(2020). They compute.
220.14(I), single or multiple receptacle on one yoke uses 180 VA per yoke Table 220.44, first band limit uses 10000 VA Table 220.44, first band factor uses 1 (demand factor) Table 220.44, remainder factor uses 0.5 (demand factor) Open MP-D1 in the panel editor