DEMO - Lantern House
Fictional 2,600 sf all-electric residence with a detached garage, heat pump, induction cooking and EV charging. Demonstration data only; no real client, person or address is represented.
Advisory engineering design check following NEC 2020 215.2(A)(1), Informational Note No. 2. The project's energy code scope is residential, so the check is not a code requirement.
Only a commercial energy code scope makes this check mandatory.
- Pass
- 25
- Fail
- 0
- REQ
- 0
- Not calculated
- 0
26 Table 9 values used here are not yet checked against the book. They still compute; rows that use one are marked.
- NFPA-70-2020/Chapter 9/Table 9/AC Resistance Uncoated Copper PVC Conduit/2/0 AWG Unreviewed data: NEC 2020 Chapter 9, Table 9, AC Resistance Uncoated Copper PVC Conduit, 2/0 AWG (0.10 ohms per 1000 ft) has not been checked against the book.
- NFPA-70-2020/Chapter 9/Table 9/XL PVC Aluminum Conduits/2/0 AWG Unreviewed data: NEC 2020 Chapter 9, Table 9, XL PVC Aluminum Conduits, 2/0 AWG (0.043 ohms per 1000 ft) has not been checked against the book.
- NFPA-70-2020/Chapter 9/Table 9/AC Resistance Uncoated Copper PVC Conduit/4 AWG Unreviewed data: NEC 2020 Chapter 9, Table 9, AC Resistance Uncoated Copper PVC Conduit, 4 AWG (0.31 ohms per 1000 ft) has not been checked against the book.
- NFPA-70-2020/Chapter 9/Table 9/XL PVC Aluminum Conduits/4 AWG Unreviewed data: NEC 2020 Chapter 9, Table 9, XL PVC Aluminum Conduits, 4 AWG (0.048 ohms per 1000 ft) has not been checked against the book.
- NFPA-70-2020/Chapter 9/Table 9/AC Resistance Uncoated Copper PVC Conduit/14 AWG Unreviewed data: NEC 2020 Chapter 9, Table 9, AC Resistance Uncoated Copper PVC Conduit, 14 AWG (3.1 ohms per 1000 ft) has not been checked against the book.
- NFPA-70-2020/Chapter 9/Table 9/XL PVC Aluminum Conduits/14 AWG Unreviewed data: NEC 2020 Chapter 9, Table 9, XL PVC Aluminum Conduits, 14 AWG (0.058 ohms per 1000 ft) has not been checked against the book.
- NFPA-70-2020/Chapter 9/Table 9/AC Resistance Uncoated Copper PVC Conduit/12 AWG Unreviewed data: NEC 2020 Chapter 9, Table 9, AC Resistance Uncoated Copper PVC Conduit, 12 AWG (2.0 ohms per 1000 ft) has not been checked against the book.
- NFPA-70-2020/Chapter 9/Table 9/XL PVC Aluminum Conduits/12 AWG Unreviewed data: NEC 2020 Chapter 9, Table 9, XL PVC Aluminum Conduits, 12 AWG (0.054 ohms per 1000 ft) has not been checked against the book.
- NFPA-70-2020/Chapter 9/Table 9/AC Resistance Uncoated Copper PVC Conduit/10 AWG Unreviewed data: NEC 2020 Chapter 9, Table 9, AC Resistance Uncoated Copper PVC Conduit, 10 AWG (1.2 ohms per 1000 ft) has not been checked against the book.
- NFPA-70-2020/Chapter 9/Table 9/XL PVC Aluminum Conduits/10 AWG Unreviewed data: NEC 2020 Chapter 9, Table 9, XL PVC Aluminum Conduits, 10 AWG (0.050 ohms per 1000 ft) has not been checked against the book.
- NFPA-70-2020/Chapter 9/Table 9/AC Resistance Uncoated Copper PVC Conduit/8 AWG Unreviewed data: NEC 2020 Chapter 9, Table 9, AC Resistance Uncoated Copper PVC Conduit, 8 AWG (0.78 ohms per 1000 ft) has not been checked against the book.
- NFPA-70-2020/Chapter 9/Table 9/XL PVC Aluminum Conduits/8 AWG Unreviewed data: NEC 2020 Chapter 9, Table 9, XL PVC Aluminum Conduits, 8 AWG (0.052 ohms per 1000 ft) has not been checked against the book.
- NFPA-70-2020/Chapter 9/Table 9/AC Resistance Uncoated Copper PVC Conduit/6 AWG Unreviewed data: NEC 2020 Chapter 9, Table 9, AC Resistance Uncoated Copper PVC Conduit, 6 AWG (0.49 ohms per 1000 ft) has not been checked against the book.
- NFPA-70-2020/Chapter 9/Table 9/XL PVC Aluminum Conduits/6 AWG Unreviewed data: NEC 2020 Chapter 9, Table 9, XL PVC Aluminum Conduits, 6 AWG (0.051 ohms per 1000 ft) has not been checked against the book.
- NFPA-70-2020/Chapter 9/Table 9/AC Resistance Uncoated Copper PVC Conduit/3 AWG Unreviewed data: NEC 2020 Chapter 9, Table 9, AC Resistance Uncoated Copper PVC Conduit, 3 AWG (0.25 ohms per 1000 ft) has not been checked against the book.
- NFPA-70-2020/Chapter 9/Table 9/XL PVC Aluminum Conduits/3 AWG Unreviewed data: NEC 2020 Chapter 9, Table 9, XL PVC Aluminum Conduits, 3 AWG (0.047 ohms per 1000 ft) has not been checked against the book.
- NFPA-70-2020/Chapter 9/Table 9/AC Resistance Uncoated Copper PVC Conduit/2 AWG Unreviewed data: NEC 2020 Chapter 9, Table 9, AC Resistance Uncoated Copper PVC Conduit, 2 AWG (0.19 ohms per 1000 ft) has not been checked against the book.
- NFPA-70-2020/Chapter 9/Table 9/XL PVC Aluminum Conduits/2 AWG Unreviewed data: NEC 2020 Chapter 9, Table 9, XL PVC Aluminum Conduits, 2 AWG (0.045 ohms per 1000 ft) has not been checked against the book.
- NFPA-70-2020/Chapter 9/Table 9/AC Resistance Uncoated Copper PVC Conduit/1 AWG Unreviewed data: NEC 2020 Chapter 9, Table 9, AC Resistance Uncoated Copper PVC Conduit, 1 AWG (0.15 ohms per 1000 ft) has not been checked against the book.
- NFPA-70-2020/Chapter 9/Table 9/XL PVC Aluminum Conduits/1 AWG Unreviewed data: NEC 2020 Chapter 9, Table 9, XL PVC Aluminum Conduits, 1 AWG (0.046 ohms per 1000 ft) has not been checked against the book.
- NFPA-70-2020/Chapter 9/Table 9/AC Resistance Uncoated Copper PVC Conduit/1/0 AWG Unreviewed data: NEC 2020 Chapter 9, Table 9, AC Resistance Uncoated Copper PVC Conduit, 1/0 AWG (0.12 ohms per 1000 ft) has not been checked against the book.
- NFPA-70-2020/Chapter 9/Table 9/XL PVC Aluminum Conduits/1/0 AWG Unreviewed data: NEC 2020 Chapter 9, Table 9, XL PVC Aluminum Conduits, 1/0 AWG (0.044 ohms per 1000 ft) has not been checked against the book.
- NFPA-70-2020/Chapter 9/Table 9/AC Resistance Uncoated Copper PVC Conduit/3/0 AWG Unreviewed data: NEC 2020 Chapter 9, Table 9, AC Resistance Uncoated Copper PVC Conduit, 3/0 AWG (0.077 ohms per 1000 ft) has not been checked against the book.
- NFPA-70-2020/Chapter 9/Table 9/XL PVC Aluminum Conduits/3/0 AWG Unreviewed data: NEC 2020 Chapter 9, Table 9, XL PVC Aluminum Conduits, 3/0 AWG (0.042 ohms per 1000 ft) has not been checked against the book.
- NFPA-70-2020/Chapter 9/Table 9/AC Resistance Uncoated Copper PVC Conduit/4/0 AWG Unreviewed data: NEC 2020 Chapter 9, Table 9, AC Resistance Uncoated Copper PVC Conduit, 4/0 AWG (0.062 ohms per 1000 ft) has not been checked against the book.
- NFPA-70-2020/Chapter 9/Table 9/XL PVC Aluminum Conduits/4/0 AWG Unreviewed data: NEC 2020 Chapter 9, Table 9, XL PVC Aluminum Conduits, 4/0 AWG (0.041 ohms per 1000 ft) has not been checked against the book.
Scroll each table sideways for the drop, allowance and state columns.
H-1
| Ckt | Description | Length (ft) | Current | Size | Drop | Allowance | Min size | Combined | State |
|---|---|---|---|---|---|---|---|---|---|
| 1 | Living and dining lighting | 45 | 12.00 A80 % of trip | 14 AWG | 2.79 %Uses 2 unreviewed Table 9 values3.35 V | 3.00 % | 14 AWGUses 26 unreviewed Table 9 values | 2.79 %Uses 2 unreviewed Table 9 values | Pass |
| 2 | Bedroom and hall lighting | 60 | 12.00 A80 % of trip | 12 AWG | 2.40 %Uses 2 unreviewed Table 9 values2.88 V | 3.00 % | 12 AWGUses 26 unreviewed Table 9 values | 2.40 %Uses 2 unreviewed Table 9 values | Pass |
| 3 | Kitchen small-appliance circuit 1 | 35 | 16.00 A80 % of trip | 12 AWG | 1.87 %Uses 2 unreviewed Table 9 values2.24 V | 3.00 % | 14 AWGUses 26 unreviewed Table 9 values | 1.87 %Uses 2 unreviewed Table 9 values | Pass |
| 4 | Exterior receptacles | 55 | 16.00 A80 % of trip | 12 AWG | 2.93 %Uses 2 unreviewed Table 9 values3.52 V | 3.00 % | 12 AWGUses 26 unreviewed Table 9 values | 2.93 %Uses 2 unreviewed Table 9 values | Pass |
| 5 | Refrigerator | 35 | 16.00 A80 % of trip | 12 AWG | 1.87 %Uses 2 unreviewed Table 9 values2.24 V | 3.00 % | 14 AWGUses 26 unreviewed Table 9 values | 1.87 %Uses 2 unreviewed Table 9 values | Pass |
| 6 | Dishwasher | 30 | 16.00 A80 % of trip | 12 AWG | 1.60 %Uses 2 unreviewed Table 9 values1.92 V | 3.00 % | 14 AWGUses 26 unreviewed Table 9 values | 1.60 %Uses 2 unreviewed Table 9 values | Pass |
| 7 | Laundry receptacle | 40 | 16.00 A80 % of trip | 12 AWG | 2.13 %Uses 2 unreviewed Table 9 values2.56 V | 3.00 % | 12 AWGUses 26 unreviewed Table 9 values | 2.13 %Uses 2 unreviewed Table 9 values | Pass |
| 8 | Bathroom receptacles | 50 | 16.00 A80 % of trip | 12 AWG | 2.67 %Uses 2 unreviewed Table 9 values3.20 V | 3.00 % | 12 AWGUses 26 unreviewed Table 9 values | 2.67 %Uses 2 unreviewed Table 9 values | Pass |
| 9,11 | Induction range | 35 | 32.00 A80 % of trip | 8 AWG | 0.73 %Uses 2 unreviewed Table 9 values1.75 V | 3.00 % | 14 AWGUses 26 unreviewed Table 9 values | 0.73 %Uses 2 unreviewed Table 9 values | Pass |
| 10,12 | Electric dryer | 40 | 24.00 A80 % of trip | 10 AWG | 0.96 %Uses 2 unreviewed Table 9 values2.31 V | 3.00 % | 14 AWGUses 26 unreviewed Table 9 values | 0.96 %Uses 2 unreviewed Table 9 values | Pass |
| 13,15 | Heat-pump outdoor unit | 30 | 24.00 A80 % of trip | 10 AWG | 0.72 %Uses 2 unreviewed Table 9 values1.73 V | 3.00 % | 14 AWGUses 26 unreviewed Table 9 values | 0.72 %Uses 2 unreviewed Table 9 values | Pass |
| 14,16 | Air handler | 25 | 16.00 A80 % of trip | 12 AWG | 0.67 %Uses 2 unreviewed Table 9 values1.60 V | 3.00 % | 14 AWGUses 26 unreviewed Table 9 values | 0.67 %Uses 2 unreviewed Table 9 values | Pass |
| 17,19 | Heat-pump water heater | 20 | 24.00 A80 % of trip | 10 AWG | 0.48 %Uses 2 unreviewed Table 9 values1.15 V | 3.00 % | 14 AWGUses 26 unreviewed Table 9 values | 0.48 %Uses 2 unreviewed Table 9 values | Pass |
| 18 | Living room receptacles | 50 | 16.00 A80 % of trip | 12 AWG | 2.67 %Uses 2 unreviewed Table 9 values3.20 V | 3.00 % | 12 AWGUses 26 unreviewed Table 9 values | 2.67 %Uses 2 unreviewed Table 9 values | Pass |
| 20 | Bedroom receptacles | 65 | 16.00 A80 % of trip | 10 AWG | 2.08 %Uses 2 unreviewed Table 9 values2.50 V | 3.00 % | 10 AWGUses 24 unreviewed Table 9 values | 2.08 %Uses 2 unreviewed Table 9 values | Pass |
| 21 | Kitchen small-appliance circuit 2 | 35 | 16.00 A80 % of trip | 12 AWG | 1.87 %Uses 2 unreviewed Table 9 values2.24 V | 3.00 % | 14 AWGUses 26 unreviewed Table 9 values | 1.87 %Uses 2 unreviewed Table 9 values | Pass |
| 22 | Smoke and CO alarms | 70 | 12.00 A80 % of trip | 12 AWG | 2.80 %Uses 2 unreviewed Table 9 values3.36 V | 3.00 % | 12 AWGUses 26 unreviewed Table 9 values | 2.80 %Uses 2 unreviewed Table 9 values | Pass |
H-GAR
| Ckt | Description | Length (ft) | Current | Size | Drop | Allowance | Min size | Combined | State |
|---|---|---|---|---|---|---|---|---|---|
| 1 | Garage lighting | 30 | 12.00 A80 % of trip | 14 AWG | 1.86 %Uses 2 unreviewed Table 9 values2.23 V | 3.00 % | 14 AWGUses 26 unreviewed Table 9 values | 3.51 %Uses 4 unreviewed Table 9 values | Pass |
| 2 | Exterior garage lighting | 40 | 12.00 A80 % of trip | 14 AWG | 2.48 %Uses 2 unreviewed Table 9 values2.98 V | 3.00 % | 14 AWGUses 26 unreviewed Table 9 values | 4.13 %Uses 4 unreviewed Table 9 values | Pass |
| 3 | Garage receptacles - east | 35 | 16.00 A80 % of trip | 12 AWG | 1.87 %Uses 2 unreviewed Table 9 values2.24 V | 3.00 % | 14 AWGUses 26 unreviewed Table 9 values | 3.51 %Uses 4 unreviewed Table 9 values | Pass |
| 4 | Garage receptacles - west | 45 | 16.00 A80 % of trip | 12 AWG | 2.40 %Uses 2 unreviewed Table 9 values2.88 V | 3.00 % | 12 AWGUses 26 unreviewed Table 9 values | 4.05 %Uses 4 unreviewed Table 9 values | Pass |
| 5 | Garage door openers | 25 | 12.00 A80 % of trip | 14 AWG | 1.55 %Uses 2 unreviewed Table 9 values1.86 V | 3.00 % | 14 AWGUses 26 unreviewed Table 9 values | 3.20 %Uses 4 unreviewed Table 9 values | Pass |
| 6 | Workbench receptacles | 20 | 16.00 A80 % of trip | 12 AWG | 1.07 %Uses 2 unreviewed Table 9 values1.28 V | 3.00 % | 14 AWGUses 26 unreviewed Table 9 values | 2.71 %Uses 4 unreviewed Table 9 values | Pass |
| 7,9 | EV charging - 24 A | 30 | 24.00 A80 % of trip | 10 AWG | 0.72 %Uses 2 unreviewed Table 9 values1.73 V | 3.00 % | 14 AWGUses 26 unreviewed Table 9 values | 2.37 %Uses 4 unreviewed Table 9 values | Pass |
| 8,10 | Small air compressor | 25 | 16.00 A80 % of trip | 12 AWG | 0.67 %Uses 2 unreviewed Table 9 values1.60 V | 3.00 % | 14 AWGUses 26 unreviewed Table 9 values | 2.31 %Uses 4 unreviewed Table 9 values | Pass |